SERIES 7200 WIRING
Master Unit with either 24 or 120 Operating Voltage
Master Unit with either
24VAC/DC or 120VAC
Operating Voltage

Master Unit with either 24 or 120 Operating Voltage
Master Unit with both
24VAC/DC Smoke Detector Input
and 120VAC Solenoid Coil Input

Notes:
All relay contacts rated 0.5 Amps @ 125VAC 60Hz; 2.0 Amps @
30VDC.
Detector Sensitivity is factory set and can only be
recalibrated by factory authorized personnel.
Detector Environmental Limits: 100°F (38°C); 95% Relative
Humidity. Cannot be installed in environments with a high concentration of corrosive
vapors or where air velocity exceeds 300 ft. per min. (91 M./min.).
Maximum wire size for Input/System Terminal Strip is 14
A.W.G.
Maximum/Minimum Operating Voltage Parameters: +10%, -15%.
|