Norton Door Control
Norton Series 7200 Electomechanical
Norton Series 7200 Electomechanical - Page 14
Norton Series 7200 Electomechanical
SERIES 7200 WIRING Master Unit with either 24 or 120 Operating Voltage Master Unit with either 24VAC/DC or 120VAC Operating Voltage
Master Unit with either 24 or 120 Operating Voltage Master Unit with both 24VAC/DC Smoke Detector Input and 120VAC Solenoid Coil Input
Notes: All relay contacts rated 0.5 Amps @ 125VAC 60Hz; 2.0 Amps @ 30VDC. Detector Sensitivity is factory set and can only be recalibrated by factory authorized personnel. Detector Environmental Limits: 100°F (38°C); 95% Relative Humidity. Cannot be installed in environments with a high concentration of corrosive vapors or where air velocity exceeds 300 ft. per min. (91 M./min.). Maximum wire size for Input/System Terminal Strip is 14 A.W.G. Maximum/Minimum Operating Voltage Parameters: +10%, -15%. |