   Norton Door Control  Norton Series 7700 Power Track  

Norton Series 7700 Power Track - Page 4

 

 

Yale Security Inc.

ORDERING POWER TRACK VOLTAGES


Ordering Power Track Voltage(s)

TYPE OF UNIT

MODEL

POWER INPUT DATA

(CAN BE) USED WITH 

NO. OF POWER INPUT LINES*

CHOICES OF VOLTAGE INPUT

MASTER

PTD-24

1

24 VOLT AC/DC

SLAVE MODEL PTS

PTD-120

1

120 VOLT AC, 60HZ.

SLAVE MODEL PTS

PTD-24DX120

2

24 VOLT AC/DC TO POWER SMOKE DETECTOR 120 VOLT AC, 60HZ. TO POWER SOLENOID

SUPPORT MODEL PT120

         

SLAVE

PTS

1

POWER SUPPLIED FROM MASTER UNIT(24VDC)

MASTER MODEL PTD-24 OR MASTER MODEL PTD-120

         

SUPPORT

PT-24

1

24 VOLT AC/DC

AREA SMOKE DETECTION SYSTEM

PT-120

1

120 VOLT AC, 60HZ

AREA SMOKE DETECTION SYSTEM OR MASTER MODEL PTD24-120

EXECUTIVE

PT-RF

1

120 VOLT AC, 60HZ

N/A

*Pairs of input lines required to supply Operating Voltage or Voltages to the unit. Pairs listed do not include signal wires to Alarm Panels nor control wires to other units' solenoids.

Operating Voltage or Voltages for the control of fire/smoke doors are specified by the architect, electrical engineer and alarm system engineer and/or contractor. Consulting with these sources will verify which operating voltage(s) should be ordered.

"PTD" Master Units have two components which require electrical power; the Integral Smoke Detector will always require 24VDC input power; the Hold-Open Solenoid can require either 24VDC input or 120VDC input. A third component, the hook-up box, receives all primary voltage inputs and distributes them to the smoke detector and the hold open solenoid.

"PTD" Master Units are available with three voltage options:

  • With PTD-24 suffix - Unit will accept either 24VAC or 24VDC power input. A rectifier in the hook-up box will rectify alternating current to direct current for operation of both the smoke detector and hold-open solenoid.
  • With PTD-120 suffix - Unit will accept 120VAC power input. A 120VAC to 24VAC transformer in the hook-up box steps the input voltage down to 24VAC . It is then recified to 24VDC for operation of both the smoke detector and the hold-open solenoid.

"PTD" Master Units Voltage Options (cont.)

  • With PTD-24D x 120 suffix - Unit must receive 24VAC or 24VDC power input. A rectifier in the hook-up box will rectify alternating current to direct current for operation of the smoke detector. Unit must also receive a 120VAC power input from a separate circuit. It is then rectified in the hook-up box to 120VDC to operate the hold-open solenoid.

Slave Units (PTS suffix) have only a hold-open solenoid which requires electrical power. They are only available with an operating voltage of 24VDC since they are only installed when they are controlled directly by the integral Smoke Detector of the Master Unit.

Support Units (PT-24 or PT-120 suffix) similarly have only a hold-open solenoid which requires electrical power. These solenoids are controlled by Smoke Detection Equipment or remote Alarm Panels. They can be ordered for operation on 24 Volt AC/DC or 120VAC, 60Hz. Support Units ( PT-24 or PT-120 suffixes ) have their hold-open solenoid operating on direct current. They have built-in rectifier that converts alternating current to direct current.


*Request for Information / Request a Catalog
 
 
 
To request more information from Norton Door Control, please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2008 AECinfo.com