 SPECIFICATIONS / FINISHES
Suggested Specification
Closer for -- doors shall be electromechanical
closer-holder. Hold-Open to be achieved by electric solenoid locking of closer arm slide
in its track. Track, arm, slide (and) solenoid (and integral smoke detector) to be
contained in a single aluminum extrusion 1-1/2" (38mm) high, 1-1/2" (38mm) deep.
Closer shall be door mounted. Track and hold-open mechanism shall be surface mounted to
the frame face for application on the pull side of the door and frame soffit mounted for
application on the push side of the door.
Single point Hold-Open shall be selective through a range
of 85º to 110º. Hold-Open point to be achieved by adjustment of a telescoping closer
arm.
Closer shall be hydraulic with full rack and pinion
enclosed in a cast aluminum alloy shell. Hydraulic fluid shall be non-gumming and
non-freezing. Closer shall have two non-critical valves to independently regulate sweep
speed and latch speed. It shall have an adjustable backcheck cushioning valve (and an
adjustable backcheck positioning valve). All valves shall be adjustable with a hex-key.
(Closer shall have spring power adjustment to permit 50% increase in closing power .)
Closer to be enclosed in a molded (Full) (Slim Style) cover.
(Master units to have an integral smoke detector with dual
ionization chamber. Master units integral smoke detector shall have latching alarm and
reset switch.) (Slave units to be controlled by the master unit.) (Support units to be
controlled by U.L. Listed Smoke Detection Equipment.) Units to be fail safe and close the
door during any interruption to the electrical power. The hold-open solenoid coil shall
have a maximum amperage draw of (.090 Amps at 24 volts) (.035 Amps at 120 volts). Unit
shall have a switch to permit testing of the releasing device function without alarming
the system.
All wiring connections shall be made without the need of
wire nuts or soldering.
Master unit(s) shall require a (24VAC-DC) (120VAC, 60Hz.)
(24VAC-DC & 120VAC, 60Hz.) power input.) (Slave unit(s) shall require a 24 Volt power
input from the Master Unit. Support unit(s) shall require a (24VAC-DC) (120VAC. 60Hz.)
power input. Supplier to coordinate electrical requirements with electrical and alarm
system engineers. Wiring (and conduit) by others.
Electromechanical Closer-Holders to be Norton Power Track
[(P)7700(PT)(PTD)(PTS)] [(P)8200(PT)(PTD)(PTS)]
[(P)8300(PT)(PTD)(PTS)] [(P)8400(PT)(PTD)(PTS)]
[(P)8500(PT)(PTD)(PTS)] Series.
Suggested Specification (Cont.)
Executive Door Holder-Release "PT-RF"
Power input to unit shall be 120 Volts AC at 60 Hz. Unit
hall have an integral radio frequency receiver. When the door is held open. the signal
from a (hand-held) (desk mounted) transmitter shall interrupt power to the unit and
release the door from hold open. Power to the transmitter shall be provided by a standard
9 Volt alkaline battery. [(P)7700PT-RF] [(P)8200PT-RF] [(P)8300PT-RF][(P)8400PT-RF]
[(P)8500PT-RF].
Finishes
Sprayed Finishes - All Norton Power Track 7700
Series/8000 Series Electromechanical Closer-Holders are available in the following sprayed
finishes. Order sprayed finishes by the Norton Symbol.
| Finish
Description |
BHMA Symbol |
Norton Symbol |
| Silver Bronze
(Alum.) Dull Bronze
Black
Gold
Dark Statuary Bronze |
689 691
693
696
690 |
AL DB
315
GB
STAT |
To Complement Duradonic |
| Medium Amber Dark Amber
Black |
694 695
693 |
312 313
315 |
Corrosion Inhibitor |
| Beige Prime
Coat* |
600 |
SRI |
*Available at extra cost. Closer-Holders can be
ordered prime coated only. i.e. (SRI) or prime coated with finish coat. i.e. (SRI) x (DB). |