architecture - engineering - construction
AECinfo.com
Printable version Bookmark this page Notify a colleague or friend about this page Bookmark and Share
  PFO Lighting   PFO Lighting  

PFO LIghting Products - Page 17

   

PFO Lighting

DIMMING SYSTEM

The HID multi-level lighting system allows fixtures to be switched two, three or four levels through motion and light sensors, or through time clocks and power line carriers to create a substantial energy savings. The system uses a state of the art switching device which can be preinstalled into new fixtures or can be sold separately for retro-fitting an existing HID fixture. This system maintains the lamps current crest factor, so the life of the lamp is not affected. The load side of the ballast is used to wire the device, so the ballast is not affected. The table below illustrates the energy savings available with each system for the most popular HID ballast's:

*LOW/HIGH          LOW-MED-LOW-MED-HIGH
LAMP INPUT HIGH MEDIUM LEVEL MEDIUM LOW LOW LEVEL
WATTAGE WATTS WATTS WATTS %SAVED WATTS %SAVED WATTS %SAVED
175 MH 215 215 170 21 135 37 110 49
250MH 295 295 166 44 125 58 97 67
400MH 460 460 203 49 190 59 150 67
1000MH 1080 1080 760 30 450 58 250 77
150HPS 190 190 140 26 93 51 45 76
250HPS 302 302 220 27 130 57 88 71
400HPS 465 465 290 38 180 61 135 71

 

CATALOG SERIES LAMP WATTAGE LAMP WATTAGE LIGHT LEVELS VOLTAGE SWITCHING SOURCE
2/WAY 150 HPS 2 120 24V
4/WAY 175 MH 3 208 120
  250   4 240 208
  400     277 240

 

 

PFO LIGHTING INC

(360)883-1154    800-577-9690      FAX(360)883-5220



Request for Information / Request a Catalog from PFO Lighting
 
 
 
To request more information from PFO Lighting, please complete the form below.
 
*Name:    
*Email:    
Company:    
*Type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.