PHOTOMETRIC DATA

P-60-D5-1 (1-Lamp, SPL)
| COEFFICIENTS
OF UTILIZATION |
| % CEILING
REFLECTANCE |
80 |
70 |
50 |
| % WALL
REFLECTANCE |
70 |
50 |
30 |
70 |
50 |
30 |
50 |
30 |
10 |
| ROOM CAVITY
RATIO |
FLOOR
CAVITY REFLECTANCE, 20% |
| 0 |
.82 |
.82 |
.82 |
.74 |
.74 |
.74 |
.60 |
.60 |
.60 |
| 1 |
.75 |
.72 |
.70 |
.68 |
.66 |
.64 |
.54 |
.52 |
.51 |
| 2 |
.69 |
.64 |
.60 |
.63 |
.58 |
.55 |
.48 |
.45 |
.43 |
| 3 |
.63 |
.57 |
.51 |
.58 |
.52 |
.47 |
.43 |
.40 |
.37 |
| 4 |
.58 |
.50 |
.45 |
.53 |
.46 |
.41 |
.38 |
.35 |
.32 |
| 5 |
.54 |
.45 |
.39 |
.49 |
.41 |
.36 |
.35 |
.31 |
.28 |
| 6 |
.49 |
.41 |
.35 |
.45 |
.37 |
.32 |
.31 |
.27 |
.24 |
| 7 |
.46 |
.37 |
.31 |
.42 |
.34 |
.29 |
.28 |
.24 |
.21 |
| 8 |
.42 |
.33 |
.27 |
.39 |
.31 |
.26 |
.26 |
.22 |
.19 |
| 9 |
.39 |
.30 |
.25 |
.36 |
.28 |
.23 |
.24 |
.20 |
.17 |
| 10 |
.37 |
.28 |
.22 |
.34 |
.26 |
.21 |
.22 |
.18 |
.15 |

P-60-D1-2 (2-Lamp,SPL)
| COEFFICIENTS
OF UTILIZATION |
| % CEILING
REFLECTANCE |
80 |
70 |
50 |
| % WALL
REFLECTANCE |
70 |
50 |
30 |
70 |
50 |
30 |
50 |
30 |
10 |
| ROOM CAVITY
RATIO |
FLOOR
CAVITY REFLECTANCE, 20% |
| 0 |
.52 |
.52 |
.52 |
.50 |
.50 |
.50 |
.48 |
.48 |
.48 |
| 1 |
.48 |
.47 |
.45 |
.47 |
.46 |
.45 |
.44 |
.43 |
.42 |
| 2 |
.45 |
.42 |
.40 |
.44 |
.41 |
.39 |
.40 |
.38 |
.37 |
| 3 |
.42 |
.38 |
.35 |
.41 |
.37 |
.35 |
.36 |
.34 |
.32 |
| 4 |
.39 |
.34 |
.31 |
.38 |
.34 |
.31 |
.33 |
.30 |
.28 |
| 5 |
.36 |
.31 |
.28 |
.35 |
.30 |
.27 |
.30 |
.27 |
.25 |
| 6 |
.33 |
.28 |
.25 |
.32 |
.28 |
.24 |
.27 |
.24 |
.22 |
| 7 |
.31 |
.26 |
.22 |
.30 |
.25 |
.22 |
.25 |
.22 |
.20 |
| 8 |
.29 |
.23 |
.20 |
.28 |
.23 |
.20 |
.23 |
.20 |
.18 |
| 9 |
.27 |
.22 |
.18 |
.26 |
.21 |
.18 |
.21 |
.18 |
.16 |
| 10 |
.25 |
.20 |
.17 |
.25 |
.20 |
.17 |
.19 |
.16 |
.15 |

| FIXTURE SERIES |
DISTRIBUTION |
MOUNTING |
LAMP ROW |
NOMINAL LENGTH
(FEET) |
RAPID START (430
MA) ADD |
OCTIC T-8 (265
MA) ADD |
LENS/LOUVER |
| P-60 |
-D1 -D2
-D3
-D4
-D5 |
-M1 (Surface) -M2 (Stem)
-M3 (Cable)
-M4 (Wall Bracket)
-M5 (Wall Spacer) |
-1 -2 |
-03 -04
-05*
-06
-08
-10*
-12 |
RS RSE
RSTW
RSETW
XRSETW |
CT CTE
CTTW
CTETW
XCTETW |
-BLA -BLW
-PRA
-SPL
-3EA |
*CT only
EMERGENCY APPLICATIONS : All fixtures are
available with Emergency Components. Specify prefix "PEL" (600
lumen output) or "PEH" (1200 lumen output).
SPECIFICATIONS
TYPE - Modular 6" quadrille
fluorescent lighting system.
LAMP : Rapid Start T-12 or Octic T-8
fluorescent (by others).
LENS/LOUVER: Available in a wide variety
of lenses/louvers.
CONSTRUCTION: Die - formed, prime quality
steel
FINISH: Baked White Enamel (standard).
Other finishes available.
LABELS: UL, IBEW.
| BLA |
Blade Louver Aluminum-Clear Anodized finish
1" high by 1"O.C. |
| BLW |
Blade Louver Aluminum-Baked White Enamel
finish 1" high by 1" O.C. |
| PRA |
Prismatic Acrylic Lens, pattern 12 |
| SPL |
Silver Parabolic Blade Louver 1.5" high
by 2.4 O.C. |
| 3EA |
Energy Saving pattern 3E Asymmetric (D4 only) |
For Aluminum Body add suffix "-AL".
For Electronic Ballast add "E"
to RS or CT.
Ex: RSE or CTE.
For a 3- or 4- lamp Electronic Ballast add
"X" to RSE or CTE.
Ex: XRSE or XCTE.
For complete listing, see Fixture Nomenclature in Technical
Data section.
 |
PRUDENTIAL LIGHTING 1774 East 21st Street, Los
Angeles, CA 90058 213.746.0360 FAX: 213.746.8838 |
|