| Notes : Refer any special conditions
to your local sales representative. (i)
Maximum allowable inside car area per ASME A17.1 Rule 207.1 and CAN/CSA-B44 3.9.
(ii) Available with SSSO or SSCO door systems.
(iii) Available with SSCO door system only.
(iv) Dimensions K (under beam), N (clear
overhead), and OH (total overhead) are based on 8'-0" (2438mm) high cab and
7'-0" (2134mm high opening. For heights larger than these, increase K, N and OH
accordingly.
(v) Dimension OH (total overhead) is based on
12" (305mm) machine beam and 4" (102mm) thick machine room slab.
(vi) Dimension P (pit depth) and M (car
overtravel) are based on full stroke buffers and Whisperflex compensation.
(vii) Reactions at E, F, G and H are based on ASME
A17.1 Rule 105.2 and CAN/CSA-B44 2.6. Weight of slab not included. Reactions based on
maximum cab weight allowed and maximum travel. Final reactions determined by elevator shop
drawings.
(viii) For rear counterweight applications,
Dimension D must increase 5" (127mm) when counterweight safety is required. For side
counterweight applications, Dimension C must increase 5" (127mm) when counterweight
safety is required. Dimension P or OH (not both), N and M may increase when cwt. safety is
used.
(ix) Dimension D must increase 11/2"
(38mm) at floors with flush transoms.
(x) Dimensions shown are for single cars. Machine
room dimensions for multicar banks will vary.
(xi) Adequate steel or concrete beam or concrete
wall supports are required for rail mounting brackets based on elevator shop drawing
loadings at each floor per ASME A17.1 Rule 200.9 and CAN/CSA-B44 3.2.5.2. Mounting and
interface between building support and rail bracket to be in agreement between customer
and elevator contractor.
(xii) Beams around hoistway to support rail
brackets to be on same vertical centerline, if possible, and to be located no further than
24" (610mm) from centerline of steel beam or edge of concrete beam or concrete wall
to platform for non-seismic applications.
(xiii) Minimum pit depth (P) for applications in
Province of Ontario is 5'-7" (1702mm).
(xiv) For front & rear applications, the
minimum floor height is 12" (305mm).
(xv) For seismic area with rear counterweight
applications, increase C by 4" (102mm) to 3500 lb (1588 kg), 6" (152mm) for 4000
lb (1814 kg) & 5000 lb (2268 kg) and increases D by 3" (76mm). For side
counterweight applications, increase C by 4" (102mm). |