Fire Guard Manufactured Panels.
Finally a Beautiful Solution to Fire Rated Window Assemblies.
Versatility
- Many patterns & sizes to choose from
- CAD Design stair step and radius applications
- Single panel applications up to 12 sq. ft.
- Underwriters Laboratory Classification: R2556
Fire Guard is:
- Versatile
- Attractive
- Pre-engineered
- Pre-manufactured
- Easy to install
Factory Assembled
Fire Guard windows are an assembly of glass block, mortar; ladder web reinforcing, panel anchors, ceramic
fiber wool expansion joints and fire stop sealant.
Fire Guard window assemblies are fully manufactured and ready for deliver. Once on site, they simply fasten into place. UL requires the
entire Fire Guard wood frame to be covered with 5/8" drywall to insulate and protect the wood from fire. This is to be done after the
units are fastened into their openings. Due to the weight factor the Fire Guard windows are limited to 12 sq. ft. Larger applications can be
manufactured in sections and joined together at the job site. On-site assembly can be done for larger applications up to 120 sq. ft. including
radius walls.

Interior Application

Exterior Application
Rough Opening Dimensions: Add 2¼" to the nominal width and height. (Example: a 24" x 30" nominal window requires a frame opening of
26¼" x 32¼").
Ratings
(minutes) |
Products Rated |
On-site Assembly |
Fire Guard™
manufactured window max. size per panel
(FT2) |
masonry wall
constr. max.
area per
panel (FT2) |
non-masonry walls max. area per panel (FT2) |
45 |
All Patterns (except Delphi)
All Sizes (except 12x12x4) |
120 |
94 |
12 (Multiple panels can be seamed
together at job site.) |
60 |
All Thickset series and Vista Brick
products only |
100 |
94 |
8 (except Vista) |
90 |
All Thickset series and Vista Brick
products only |
100 |
not approved |
not approved |
Additional products not rated:
- All Corner, End Block, or Argue
- All Pavers
- Frosted Blocks
|
|