architecture - engineering - construction
Standard Refrigeration Co.
Evaporator
Evaporator - Page 4
Evaporator
| Serviceable Compact 
TX
design features
&
ratings |
| References |
| specifications |
95-98 |
| capacities |
99-101 |
| sizing |
92-93 |
| gasket cross reference |
126 |
| gasket ID |
127 |
| codes |
152 |
| custom
designs |
155 |
 |
- Serviceable
- 30% - 50% smaller than comparable models
- Easier to handle and position
- New advanced design
- UL listed or ASME
- 3/4 insulation
- Single and dual circuit designs
- 23 TX models from 2 thru 120 tons
Conformance
Standard TX2-TX25 chiller barrels are U.L. listed for 225
psi tube side and 150 psi shell side working pressures. TXB30-TXB120 units are constructed
to ASME standards for 225 psi tube side and 250 psi shell side working pressures. Each
unit is tested before shipment and ratings are developed through extensive laboratory
testing and computer modeling.
Nominal Tonnage Rating Basis
Nominal ratings are based on ARI standard 480, specific
conditions being:
| 1 ton = 12,000 Btu/hr |
100°F. liquid entering TXV |
| 54°F. inlet water |
7° superheat |
| 44°F. outlet water |
35°F R22 Saturated Suction |
0.00025ft2 hr °F/Btu additive fouling factor (total
0.0005ft2 hr °F/Btu)
Limitations
- For cooling water
applications a minimum evaporating temperature of 32°F. should be maintained in the
evaporator to prevent freezing.
- Maximum water entering temperature of 70°F.
- Minimum outgoing water temperature of 36°F.
- Minimum approach 5° (for approaches 6° or less, system
should be designed to insure
proper oil return).
Note: For brine, low temperature and special design applications, please consult factory
for complete technical assistance.
Technical Assistance and Custom Designs
Standard offers custom design services and computer
performance projections on all heat exchange products to help you match product and
application accurately. You are invited to contact your nearest sales representative or
our office headquarters for prompt assistance. |