INSTALLATION AND OPERATING INSTRUCTIONS |
MODELS: SW-35 TO SW-112
PRE-INSTALLATION:
1. Determine correct model for the cubic
feet of enclosure (see chart).
Note: Certain wall materials, excessive glass, ceiling over 8", inadequate insulation
or adjoining outside walls may require that a model larger than the cubic feet of the
enclosure be used. Steam-Whirl is available for assistance in selecting the correct size
unit.
2. Check that electrical power supply
available is adequate for the voltage, amps and phase of the unit.
3. Carton contains (1) steam generator,
(1) steamhead & escutcheon and (1) standard timer unless otherwise requested.
4. Do not expose generator to outside
weather conditions or freezing temperatures.
HELPFUL HINTS FOR NEW CONSTRUCTION OR RENOVATION:
1. Ceiling should be pitched away from the
door 1 1/2" per foot or constructed in a gable configuration.
2. Enclosures should not be vapor proof. A
slight opening of approximately 1/4" is desired to create movement of the steam.
3. Any exposed plaster, plaster-board or
sheet rock surfaces must be well sealed with a commercial quality waterproof sealer.
| Model |
Maximum
Cubic Feet
of Enclosure |
KW |
Volts |
Phase |
Amps |
Breaker
Size |
Wire
Size |
| SW - 35 |
60 |
3.5 |
240 |
1 |
15 |
20A |
12AWG |
| SW - 50 |
80 |
5 |
240 |
1 |
21 |
30A |
10AWG |
| SW - 50 - 8 |
208 |
1 |
24 |
30A |
10AWG |
| SW - 65 |
140 |
6.5 |
240 |
1 |
27 |
40A |
8AWG |
| SW - 65 - 8 |
208 |
1 |
31 |
40A |
8AWG |
| SW - 75 |
220 |
7.5 |
240 |
1 |
31 |
40A |
8AWG |
| SW - 75 - 8 |
208 |
1 |
36 |
50A |
8AWG |
| SW - 90 |
300 |
9 |
240 |
1 |
38 |
50A |
8AWG |
| SW - 90 - 3 |
240 |
3 |
22 |
30A |
10AWG |
| SW - 90 - 83 |
208 |
3 |
25 |
30A |
10AWG |
| SW - 110 |
340 |
10 |
240 |
1 |
42 |
60A |
6AWG |
| SW - 112 |
400 |
11.5 |
240 |
1 |
47 |
60A |
6AWG |
c |
 |
|