INSTALLATION AND OPERATING INSTRUCTIONS |
CLASSIC SERIES
MODELS: SW-35, SW-50, SW-65, SW-75, SW-90, SW-110, SW-112
PRE-INSTALLATION:
1. Determine that you purchased the
correct model for the cubic feet of enclosure (see chart).
2. Check that electrical power supply
available is adequate for the voltage, amps and phase of the unit.
3. Carton contains (1) unit, (1)
timer, (1) steamhead & escutcheon.
4. New construction or renovation,
ceilings should be pitched away from door 11/2" per foot or a gable
configuration.
5. Enclosures should not be vapor-proof. A
slight opening of approximately 1/2 " would be desired. Any exposed plaster,
plaster-board or sheet rock surfaces must be well sealed with a commercial quality
waterproof sealer.
6. Generator cannot be exposed to outside
conditions.
IMPORTANT. After
following installation instructions on next page, allow 20-30 seconds for unit to have any
reaction.
| Model |
Maximum
Cubic Feet
of Enclosure |
KW |
Volts |
Phase |
Amps |
Breaker
Size |
Wire
Size |
| SW - 35 |
60 |
3.5 |
240 |
1 |
15 |
20A |
12AWG |
| SW - 50 |
80 |
5 |
240 |
1 |
21 |
30A |
10AWG |
| SW - 50 - 8 |
208 |
1 |
24 |
30A |
10AWG |
| SW - 65 |
140 |
6.5 |
240 |
1 |
27 |
40A |
8AWG |
| SW - 65 - 8 |
208 |
1 |
31 |
40A |
8AWG |
| SW - 75 |
220 |
7.5 |
240 |
1 |
31 |
40A |
8AWG |
| SW - 75 - 8 |
208 |
1 |
36 |
50A |
8AWG |
| SW - 90 |
300 |
9 |
240 |
1 |
38 |
50A |
8AWG |
| SW - 90 - 3 |
240 |
3 |
22 |
30A |
10AWG |
| SW - 90 - 83 |
208 |
3 |
25 |
30A |
10AWG |
| SW - 110 |
340 |
10 |
240 |
1 |
42 |
60A |
6AWG |
| SW - 112 |
400 |
11.5 |
240 |
1 |
47 |
60A |
6AWG |
NOTE:
Certain wall materials, excessive glass, windows, skylights,
Ceilings over 7', inadequate insulation, adjoining outside walls may require that a model
larger than the cubic feet of the enclosure be used. If in doubt, contact the factory
direct for assistance in selecting the correct size unit.
|