Equipment Rooms
ConCore®
BENEFITS

- Excellent rolling load performance
- Superior ultimate load performance
- Interchangeable with other panel strengths
- Flame spread and smoke development rating: Class A
- Painted finish for lifetime protection
- Solid and quiet
- Completely non-combustible
- Excellent grounding and electrical continuity
UNDERSTRUCTURE OPTIONS

2' & 4' Bolted Stringer Systems

Snap-On Stringer System
CONCORE® PERFORMANCE SELECTION CHART
| SYSTEM TYPE |
SYSTEM
WEIGHT |
STATIC
LOADS |
ROLLING
LOADS |
IMPACT
LOADS |
| Panel |
Understructure |
Concentrated Loads |
Uniform
Loads |
Ultimate
Loads * |
10 Passes |
10,000
Passes |
| ConCore®
1000 |
Bolted Stringer |
9.0 lbs./ft2
44 kg/m2 |
1000 lbs. 454 kg |
250 lbs. 113 kg |
Min. 2.5 |
800 lbs. 363 kg |
600 lbs. 272 kg |
150 lbs. 68 kg |
| ConCore®
1250 |
Bolted Stringer |
9.5 lbs./ft2
46 kg/m2 |
1250 lbs. 567 kg |
300 lbs. 136 kg |
Min. 2.5 |
1000 lbs. 454 kg |
800 lbs. 363 kg |
150 lbs. 68 kg |
| ConCore®
1500 |
Bolted Stringer |
10 lbs./ft2
49 kg/m2 |
1500 lbs. 680 kg |
375 lbs. 170 kg |
Min. 2.5 |
1250 lbs. 567 kg |
1000 lbs. 454 kg |
150 lbs. 68 kg |
| ConCore®
2000 |
Bolted Stringer |
11.5 lbs./ft2
56 kg/m2 |
2000 lbs. 907 kg |
500 lbs. 227 kg |
Min. 2.5 |
1500 lbs. 680 kg |
1250 lbs. 567 kg |
150 lbs. 68 kg |
| ConCore®
2500 |
Bolted Stringer |
12.0 lbs./ft2
59 kg/m2 |
2500 lbs. 1134 kg |
625 lbs. 284 kg |
Min 2.5 |
1500 lbs. 680 kg |
2000 lbs. 907 kg |
150 lbs. 68 kg |
Note: Concentrated, ultimate, and impact loads are
applied on a one square inch area point load. Results above indicate weakest point of
panel. Other strengths available-consult factory. For further information and product
specifications call the Tate Hotline @ 1-800-231-7788.
* Panel shall be capable of withstanding without
failure a minimum safety factor of 2.5 applied to the panel's concentrated load rating.

|