All Steel

Perforated Airflow Panel (with or without damper)

Solid panel

BENEFITS
- Lightweight for ease of handling
- Excellent ultimate load performance
- Painted finish for lifetime protection
- Interchangeable with other panel strengths
- Completely non-combustible
- Excellent grounding and electrical continuity
- Flame spread and smoke development rating: Class A
ALL STEEL PERFORMANCE SELECTION CHART
| SYSTEM TYPE |
SYSTEM
WEIGHT |
STATIC
LOADS |
ROLLING
LOADS |
IMPACT
LOADS |
| Panel |
Understructure |
Concentrated
Loads |
Uniform
Loads |
Ultimate
Loads * |
10 Passes |
10,000
Passes |
| All Steel
1000 |
Bolted Stringer |
6.0 lbs./ft2 30 kg/m2 |
1000 lbs. 454 kg |
250 lbs. 113 kg |
Min. 2.5 |
400 lbs. 181 kg |
400 lbs. 181 kg |
150 lbs. 68 kg |
| All Steel
1250 |
Bolted Stringer |
7.0 lbs./ft2 35 kg/m2 |
1250 lbs. 567 kg |
300 lbs. 136 kg |
Min. 2.5 |
500 lbs. 227 kg |
500 lbs. 227 kg |
150 lbs. 68 kg |
| All Steel
1500 |
Bolted Stringer |
8.5 lbs./ft2 41 kg/m2 |
1500 lbs. 680 kg |
375 lbs. 170 kg |
Min. 2.5 |
600 lbs. 272 kg |
600 lbs. 272 kg |
150 lbs. 68 kg |
Note: Concentrated, ultimate, and impact loads are
applied on a one square inch area point load. Results above indicate weakest point of
panel. Other strengths available-consult factory. For further information and product
specifications call the Tate Hotline @ 1-800-231-7788.
* Panel shall be capable of withstanding without
failure a minimum safety factor of 2.5 applied to the panel's concentrated load rating.
UNDERSTRUCTURE OPTIONS

2' & 4' Bolted Stringer Systems

Snap-On Stringer System |