| Controls Data and Connections Safeties
Smart shutdown sequence condenser/absorber loss of
flow
Low condenser/absorber water temperature
High interstage pressure limit
High pressure cutout
Evaporator leaving fluid temperature cutout
Motor current overload
High motor winding temperature
Over/under voltage (optional)
Purge limit
Sensor failure detection
Monitored Points
Chiller information is available at the operator interface
via a clear language display. Access to the information is through four dedicated report
keys:
Customer, Chiller, Cycle and Pump/Purge.
Customer Report
User defined custom report (operator may choose up to 20
points from a list of over 100 choices).
Chiller Report
Status, fluid temperatures, and setpoints:
Operating mode (i.e. run status)
Chilled water setpoint
Evaporator entering/leaving water temperatures
Absorber entering/leaving water temperatures
Condenser leaving water temperature outdoor air
temperature
Evaporator leaving water temperature
Chilled water reset
Cycle Report
Refrigerant temperatures and pressures:
Solution temperature leaving high temperature
generator
Interstage vapor temperature
Solution temperature entering level control
Mixed solution temperature entering low temperature
heat exchanger
Solution temperature entering high temperature
generator
Interstage vapor pressure
High temperature generator leaving concentration
Low temperature generator leaving concentration
High temperature generator cutout and monitor
temperature
Crystallization detection temperature
Crystallization trip temperature
Solution temperature leaving low temperature
generator
Saturated condenser refrigerant temperature
Absorber entering concentration
LiBr crystallization margin
Solution temperature leaving absorber
Absorber spray temperature
Solution temperature leaving absorber
Solution temperature entering low temperature
generator
Saturated evaporator refrigerant temperature
Evaporator leaving water temperature
Evaporator entering water temperature
Absorber entering water temperature
Absorber leaving water temperature
Condenser leaving water temperature
Solution pump auto/manual speed command
Energy input auto/manual/slaved reported command
Steam Supply Pressure
Generator Steam Pressure
Pump/Purge Report
Solution pump
Starts and hours counters
Motor phase currents
Motor phase voltages (optional)
Purge Pump
Operating mode and status
Refrigerant suction temperature
Pumpout rate
Total pumpout time
Service log
Diagnostics
The absorption chiller Unit Control Panel (UCP2) provides
over 70 active and historic diagnostics such as:
Water and refrigerant/solution temperatures out of
range
Solution pressures out of range
Loss of system water flows
Sensor and switch faults
Overload trips
Over/under voltage (optional)
Crystallization recovery
High pressure cutout
Emergency stop
Loss of communication to other modules
Motor abnormal
Operator Interface
The Trane Horizon steam-fired absorption chiller
control panel, UCP2, is easy to use, understand, access information, read, change
setpoints, diagnose problems, maintain, and to reset after shutdown.
Convenience
Enunciation of all information is at the front panel
display (including power, voltage, amps, purge pressures, and number of starts data).
Messages displayed using clear language.
Readability
Two line, 40 character display that is easy to read
from within a 60 degree angle
LCD backlight so that the display can be read in a
variety of equipment room lighting
Remote Operator Interface
With the addition of an optional remote interface panel, up
to four chillers with UCP2 can be monitored and controlled. All data available at each
chillers local operator interface is available to the Remote Operator Interface via
a single twisted pair.
Ease of Use
Keypad programmability no manual switches or
setpoint potentiometers
Logically arranged report groups with report header
and setpoint groups
Selectable security
Variable points updated every two seconds
Messages that direct user to problem source via a
menu item
Application Flexibility
Seven languages available
Metric (SI) units available
Complete character human interface available
Trane ICS Compatibility
The Trane Absorption chiller control panel, UCP2, is 100
percent compatible with the Trane Integrated Comfort systems, ICS, UCP2 easily integrates into the Tracer ® family of flexible
chiller plant system controllers with a single twisted-wire pair communications cable.