| Mechanical Specifications Power Panel
A factory wired and mounted power panel shall include: main
power connection, control transformer and 115 volt single phase control circuit. Unit
shall be available for operation on 200, 230, 460 or 575 volts, 3-phase, 60 hertz power or
190, 220, 380 or 415 volts, 3-phase, 50 hertz power.
Control Panel
The unit control panel (UCP2) is a microprocessor-based
chiller control system that provides complete standalone operation. The UPC2 shall provide
the following items:
Control Functions
Chilled water temperature control
Concentration Control
System Features and Functions
User interface with a 40 character, two line display
and a 16 key keypad, capable of displaying 7 languages and SI or English units
Passwords for protection of unit setup and
configuration
Chilled water pump control
Absorber/Condenser pump control
Automatic and manual control of solution and
refrigerant pumps
Solution flow control of the low temperature
solution pump and absorber pump via an adjustable frequency drive
Anti-crystallization through dilution control
Automatic and manual purge system
Chilled water reset
Two-way valve assembly for hot water flow control or
steam flow control
Adaptive Limits
Evaporator water temperature limit
High interstage pressure limit
High interstage temperature limit
Low absorber/condenser limit
Soft-loading control
System Protection
Evaporator freeze protection
Chilled water flow confirmation
Cooling water flow confirmation
High interstage pressure cutout to prevent excessive
pressure
Emergency stop/shutdown
Monitor and Displays
Chilled water temperature entering and leaving
Absorber/Condenser water temperature entering and
leaving
Evaporator water flow (opt)
Cooling water flow (opt)
Solution concentrations
Solution temperatures
Interstage pressure
Total motor current
Unit voltage
Chiller run time and starts
Purge operation and run time
Interfaces to UCP2
Interface to Tracer ICS Systems
External machine manual reset alarm indication
output
External machine auto reset warming indication
output
External limit warning indication output
Interstage pressure relief request output
Maximum capacity indication output
External auto-stop/emergency shutdown
External chilled water setpoint (opt)
Tracer temperature sensor (opt)
Tracer controlled relay (opt) |