   Trane Company (The)  Building Management Systems  

Building Management Systems - Page 15

 

 

Building Management Network

Building Management Network (BMN) is a software package used to communicate with Tracer and Tracker panels. These panels may be located in the same facility or in different remote facilities.

ICS Capability

BMN’s communication capabilities make detailed ICS information available. With BMN’s dynamic interface, an operator can monitor and control up to 120 independent Tracer and Tracker systems. BMN receives specific mechanical equipment alarm data as it occurs from remote unit controllers via modem or from equipment in the same building. BMN provides detailed diagnostic information unique to the equipment involved, including probable servicing solutions. BMN can also dial out to remote ICS locations automatically each day to collect specific point data and usage reports. Any modification to schedules or setpoints for a group of buildings can be easily implemented across all Tracer systems.

Software Capabilities

BMN offers the following software capabilities:

  • An event log retains a historical record of events, including alarms.
  • Reports provide the operator with access to important energy and billing data. The following types of reports are available:
    — Daily and monthly energy usage reports
    – HVAC unit controller and zone status reports
    — Weekly and monthly after hours usage reports
  • A trend log retains a historical  record of values for specified points. This information often provides troubleshooting answers for service technicians.
  • Operator-defined maintenance messages can be used with alarms or equipment run time limits to help schedule preventive maintenance.
  • Save and restore software saves programming from a Tracer or Tracker panel to a disk. A remote panel can be reprogrammed later by downloading the saved programming.
  • Optional color graphics display point information from Tracer panels on customized dynamic color graphics. The color graphics software operates using a mouse and function keys with pop-up menus. Color graphics are not available with Tracker panels.
    Background graphics can be created using a generic graphics package, or they can be used from the supplied graphics library. This library includes graphics of HVAC equipment such as fans, pumps, valves, chillers, and VAV terminal units.
  • An optional scheduling feature allows an operator to schedule up to 120 Tracer 100 series panels using the power of the PC. This simplifies schedule setup and allows for advance scheduling of zones. This option also allows for easy shutdown of multiple buildings in an emergency.
    Refer to the Tracer 100 Series Systems and Tracker and VariTrac Zoning System sections of this catalog for more information about the capabilities available through BMN.

Hardware Description

BMN runs on a PC with a 80386 or higher processor. A modem is required at the PC for remote connections via a telephone line. A direct-connect cable is used if the PC is directly wired to a Tracer or Tracker panel.

BMN can establish remote communications (via modem) with up to 120 different building management panels.

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2009 AECinfo.com