DDC Chiller Sequencer

The DDC Chiller Sequencer is a sequencing panel that provides start/stop control of two chillers and associated pumps, setpoint control, lead/lag, soft loading, failure recovery, chilled water reset, and ice making mode.

Software Capabilities

  • System enable - A contact closure input to the panel selects either enable or disable mode. This input is typically connected to a time clock for time of day scheduling, but can be wired to a MANUAL/OFF/AUTO switch and thermostat to provide an ambient interface.
  • Chiller/pump control. The DDC Chiller Sequencer provides binary outputs to control two chillers and two pumps.
  • Lead/lag control. The operator can select manual or automatic chiller rotation through the panel keypad. Automatic rotation forces daily rotation at midnight. In the manual rotation mode, a separate manual 2-position switch is used to determine the lead chiller.
  • Soft loading prevents unnecessary operation of the lag chiller on initial system startup.
  • Failure recovery.
    In the event of
    a chiller failure, the lag chiller starts (through a normal Add program) when the system supply water temperature exceeds setpoint. The sequencer turns on its alarm output if:
    • the system setpoint is exceeded for an extended period of time,
    • a sensor fails,
    • the DDC Chiller Sequencer loses power,
    • or the DDC Chiller Sequencer has a power failure,
  • Setpoint control (optional).
    The operator can enter the system setpoint through the sequencing panel keypad. The sequencing software sends a setpoint to each chiller. No manual setpoint coordination is required. .
  • Common leaving water control for one-pump systems.
    The individual chiller setpoint is
    automatically adjusted to maintain the common leaving water temperature at setpoint in 1-pump systems with one chiller enabled (constant flow through both chillers)
  • Chilled water reset resets the system setpoint based on either return water temperature or a separate reset sensor input as determined in system setup.

Hardware Description

The DDC Chiller Sequencer package consists of a Trane 20-point PCM with LCD and keypad, a matched pair of thermistor sensors, and the sequencer software.

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2009 AECinfo.com