| Application Considerations b
Provide Vertical Clearance
Vertical condenser air discharge must be unobstructed. While it is difficult to predict the degree of warm air recirculation,
a unit installed as shown below would have its capacity
and efficiency significantly reduced possibly to the degree of nuisance high head pressure tripouts. Performance data
is based on free air discharge

c
Provide Lateral Clearance
The condenser coil inlet must not be obstructed. A unit installed closer than the minimum recommended distance to a wall or
other vertical riser may experience a combination of
coil starvation and warm air recirculation, resulting in unit capacity and efficiency reductions and possible excessive head pressures.
The recommended lateral clearances are depicted in the dimensional data section.
These are estimates and should be reviewed with the
local Trane sales engineer at the jobsite.

d
Provide Sufficient Unit-to-Unit Clearance
Units should be separated from each other by sufficient distance to prevent warm air recirculation or coil starvation. Doubling
the recommended single unit air-cooled chiller
clearances will generally prove to be adequate.
e
Walled Enclosure Installations
When the unit is placed in an enclosure or small depression, the top of the
fans should be no lower than the top of the enclosure
or depression. If they are, consideration should be given to ducting the top of the unit. Ducting individual fans, however, is
not recommended. Such applications should always be
reviewed with the local Trane sales engineer. Minimum operating ambient temperatures for standard unit

VOLTAGE
Nominal voltage is the nameplate rating voltage. The actual range of line voltages
at which the equipment can satisfactorily operate are
given below.
| Rated Voltage |
Voltage
Utilization Range |
| 200 |
180-220 |
| 208-230 |
187-253 |
| 230 |
208-254 |
| 380 |
342-418 |
| 400 |
360-440 |
| 415 |
374-456 |
| 460 |
414-508 |
WATER TREATMENT
Dirt, scale, products of corrosion, and other foreign material in the water will adversely affect heat transfer between the
water and system components. Foreign matter in the
chilled water system can also increase pressure drop and, consequently, reduce waterflow.
Proper water treatment must be determined locally and
depends on the type of system and local water characteristics.
Do not use salt or brackish water in Trane chillers. Use of either will lead to a shortened life. The Trane Company
encourages the employment of a reputable water treatment specialist, familiar with local water conditions, to assist in the establishment
of a proper water treatment program.
The capacities given in the "Performance Data" section of this catalog
are based on water with a fouling factor of 0.00025
(per ARI 590- 92). For capacities at other fouling
factors, see "Performance Adjustment Factors" section of this catalog.
EFFECT OF ALTITUDE ON CAPACITY
Chiller capacities given in the "Performance Data" section are based upon
application at sea level. At elevations substantially
above sea level, the decreased air density will decrease condenser capacity and, therefore,
unit capacity and efficiency. The adjustment factors in
the "Performance Adjustment Factors" section of this catalog can be applied directly to the performance data to determine
the units adjusted performance.
AMBIENT LIMITATIONS
Trane chillers are designed for year-round applications in ambients from 0°F
to 115°F. For operation below 0°F or above 115°F,
contact the local Trane sales office. If hot gas bypass
is used, operating ambients vary depending upon unit size (see the "General
Data" section of this catalog).
1 Low Ambient
Operation
Start-up and operation of Trane chillers at lower ambient temperatures
require that sufficient head pressure be maintained for proper expansion valve operation. |