Homepage  
Search
find:
search for:
   
 
Site Navigation
News / Publications
Jobs
Service
   Add this page to Google Bookmarks
   Add this page to Mister Wong
   Add this page to del.icio.us
 
   Trane Company (The)  Air Cooled Liquid Chillers  

Air Cooled Liquid Chillers - Page 11

 

 

Application Considerations

Minimum operating ambient temperatures for standard unit selections and units with hot gas bypass are shown in the "General Data" section of this catalog.

Minimum ambient temperatures are based on still conditions (winds not exceeding five mph). Greater wind velocities will result in a drop in head pressure, therefore increasing the minimum starting and operating ambient temperatures.

Optional low ambient units use a electronic low ambient damper control (20-60 tons) or a variable speed fan motor (10-15 tons) arrangement to control condenser capacity by modulating condenser fans in response to refrigerant pressure.

2 High Ambient Operation

Maximum cataloged ambient temperature operation of a standard Trane chiller is 115°F. Operation at design ambients above 115°F can result in excessive head pressures. For operation above 115°F, contact your local Trane sales office.

CONTROLS

1 Temperature Controller

In order to provide stable system operation and to prevent excessive compressor cycling, the temperature control sensor in all 20-60 ton chillers is located in the supply (outlet) solution. The temperature sensor in all 10 and 15 ton chillers is located in the return (inlet) solution. This sensor cannot be relocated. Doing so would result in improper unit operation.

2 Anti-recycle Timer/Fixed-Off Timer

All IntelliPak air-cooled chillers come standard with Anti-recycle/Fixed Off Timers. This function prevents rapid cycling of the compressors due to low load conditions or short water loops.

3 Pumpdown

CGAF air-cooled chillers will pumpdown, if function is enabled, when a refrigerant circuit is turned off. All of the refrigerant is pumped into the condenser. A solenoid valve provides a positive shutoff between the condenser and the evaporator, allowing little or no refrigerant migration to the evaporator during "off" periods.

4 Hot Gas Bypass

Hot gas bypass provides more stable leaving solution temperature control at light load conditions. The compressor runs continuously for a user-defined run time. Minimum starting and operating ambients with hot gas bypass are shown in the "General Data" section of this catalog. The hot gas bypass reduces the unit head pressure, thereby increasing the minimum operating ambient.

5 Loss of Flow Protection

Loss of flow may result in evaporator freeze up. Full chilled solution flow must be maintained through the evaporator while compressors are operating. A flow switch used as a safety interlock is always recommended for CGA units. The CGAF air-cooled chiller has a system which senses a loss of flow condition and shuts the unit down. The CGAF’s microcomputer is automatically reset for the unit to resume operation. A set of contacts is available for externally starting and stopping the pump

WATERFLOW LIMITS

The minimum water flow rates are given in the "General Data" section of this catalog. Evaporator flow rates below the tabulated values will result in laminar flow causing scaling, stratification, freeze-up problems, and poor temperature control. The maximum evaporator water flow rate is given in the "General Data" section. Flow rates exceeding those listed will result in excessive tube erosion and very high pressure drop across the evaporator. Trane recommends that constant water flow be maintained at all times through the evaporator. Because the temperature controller strictly senses temperature, variable flow through the evaporator may result in loss of control and localized freezing or nuisance low temperature cutouts. Consult your local Trane sales engineer if your application requires varying flows.

TEMPERATURE LIMITS

1 Leaving Solution Temperature range

The minimum leaving solution temperature setpoint is dependent on the number of capacity stages and the temperature difference across the evaporator. Water supply temperature setpoints less than these values result in suction temperatures at or below the freezing point of cold water.

A glycol solution is required for operation below the recommended minimum setpoints. Refer to the "Performance Adjustment Factors" section of this catalog to determine the minimum leaving chilled solution setpoint and adequate ethylene glycol concentration for safe operation.

The maximum catalog leaving solution temperature from the evaporator is 65°F for outdoor ambients up to 115°F. High leaving water temperatures exceeding this may result in excessive suction temperatures and, therefore, inadequate motor cooling. For applications requiring high leaving water temperatures, contact your local Trane sales office for suggested alternatives.

The maximum water temperature that can be circulated through an evaporator, when the unit is not operating, is 108°F (100°F for CGA 8, 10, 12½ and 15 ton chillers). The evaporator becomes thermal stress limited at these temperatures.

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2009 AECinfo.com