Trane Company (The)
Air Cooled Liquid Chillers
Air Cooled Liquid Chillers - Page 12
Air Cooled Liquid Chillers
| Application Considerations 2 Supply Water Temperature Drop The performance data for Trane chillers is based on a chilled water Application Considerations selections and units with hot gas bypass are shown in the "General Data" section of this catalog. 13 Application Considerations temperature drop of 10°F. Temperature drops outside this range will result in unit performance that differs from that cataloged. For performance data outside the 10°F range see the "Performance Adjustment Factors" section in this catalog. Chilled water temperature drops from 6 to 18°F (8 to 12°F in CGA units) may be used as long as minimum and maximum water temperature and minimum and maximum flow rates are not violated. Temperature drops outside 6 to 18°F (8 to 12°F in CGA units) are beyond the optimum range for control and may adversely affect the controllers capability to maintain an acceptable supply water temperature range. Further, temperature drops of less than 6°F may result in inadequate refrigerant superheat. Sufficient superheat is always a primary concern in any direct expansion refrigeration system and is especially important in a package chiller where the evaporator is closely coupled to the compressor. When temperature drops are less than 6°F, an evaporator runaround loop may be required. TYPICAL WATER PIPING All building water piping must be flushed prior to making final connections to the chiller. To reduce heat loss and prevent condensation, insulation should be applied. Expansion tanks are also usually required so that chilled water volume changes can be accommodated. A typical piping arrangement is shown on the following page. SHORT WATER LOOPS The proper location of the temperature control sensor is in the supply (outlet) water for 20-60 ton chillers and in the return (inlet) water for 8, 10, 12½ and 15 ton chillers. This location allows the building to act as a buffer and assures a slowly changing return water temperature. If there is not a sufficient volume of water in the system to provide an adequate buffer, temperature control can be lost, resulting in erratic system operation and excessive compressor cycling. A short water loop (less than one minute in duration) will lead to erratic system operation. To prevent the effect of a short water loop, the following items should be given careful consideration:
MULTIPLE UNIT OPERATION Whenever two or more units are used on one chilled water loop, Trane recommends that their operation be controlled from a single control device, such as a Trane Tracer® system. The "Stand-alone" alternative is the DDC Chiller Sequencer.
|




