Trane Company (The) Air Cooled Liquid Chillers Air Cooled Liquid Chillers - Page 22
| Performance Data - 60 Hz 10-60 Part
Load Table 23-1 - Part Load Data, ARI
Points (10-60 Tons)
| |
|
|
Entering Condenser Air Temperature (Degrees F) |
| |
|
|
95 |
87 |
85 |
79 |
75 |
71 |
67 |
65 |
| Ton |
Model Number |
|
100 % Load |
80 % Load |
75 % Load |
60 % Load |
50 % Load |
40 % Load |
30 % Load |
25 % Load |
| 10 |
CGA 120 |
EER
Capacity (Tons) KW Input |
9.4 |
- |
- |
- |
11.5 |
- |
- |
- |
| 8.7 |
- |
- |
- |
4.8 |
- |
- |
- |
| 11.1 |
- |
- |
- |
5.0 |
- |
- |
- |
| 15 |
CGA 180 |
EER
Capacity (Tons) KW Input |
9.1 |
- |
- |
- |
10.3 |
- |
- |
- |
| 13.7 |
- |
- |
- |
7.0 |
- |
- |
- |
| 18.0 |
- |
- |
- |
8.2 |
- |
- |
- |
| 20 |
CGAF-C20 |
EER
Capacity (Tons) KW Input |
9.6 |
- |
- |
- |
13.8 |
- |
- |
- |
| 17.3 |
- |
- |
- |
10.2 |
- |
- |
- |
| 21.6 |
- |
- |
- |
8.9 |
- |
- |
- |
| 25 |
CGAF-C25 |
EER
Capacity (Tons) KW Input |
9.6 |
- |
- |
12.9 |
- |
13.5 |
- |
- |
| 23.0 |
- |
- |
15.8 |
- |
10.9 |
- |
- |
| 28.6 |
- |
- |
14.7 |
- |
9.7 |
- |
- |
| 30 |
CGAF-C30 |
EER
Capacity (Tons) KW Input |
9.6 |
- |
- |
- |
13.0 |
- |
- |
- |
| 27.4 |
- |
- |
- |
16.2 |
- |
- |
- |
| 34.1 |
- |
- |
- |
14.9 |
- |
- |
- |
| 40 |
CGAF-C40 |
EER
Capacity (Tons) KW Input |
9.6 |
- |
11.6 |
- |
14.0 |
- |
- |
15.4 |
| 33.8 |
- |
27.4 |
- |
20.3 |
- |
- |
10.3 |
| 42.2 |
- |
28.4 |
- |
17.3 |
- |
- |
8.0 |
| 50 |
CGAF-C50 |
EER
Capacity (Tons) KW Input |
9.6 |
11.1 |
- |
12.9 |
- |
- |
14.9 |
- |
| 42.3 |
36.1 |
- |
29.3 |
- |
- |
14.9 |
- |
| 52.7 |
39.0 |
- |
27.3 |
- |
- |
12.0 |
- |
| 60 |
CGAF-C60 |
EER
Capacity (Tons) KW Input |
9.6 |
- |
11.7 |
- |
14.6 |
- |
- |
16.1 |
| 55.9 |
- |
45.7 |
- |
34.3 |
- |
- |
17.3 |
| 69.7 |
- |
46.9 |
- |
28.2 |
- |
- |
12.9 |
Notes:
1. Data is rated in accordance with ARI Standard 590-92, Section
7.3.
- 44°F leaving chilled water temperature.
- (55°F + 0.4°F x % Load) = entering ambient temperature.
- Constant evaporator waterflow as determined at full load operation at
95°F and 10°F evaporator temperature drop.
- % Load by compressor displacement as defined by ARI Standard 590-92.
2. EER = Energy Efficiency Ratio, (Btu/watt-hour). Power inputs
include compressors, condenser fans and control power.
Table 23-2
Integrated Part Load Values
| Tons |
Model Number |
IPLV |
| 10 |
CGA 120 |
10.8 |
| 15 |
CGA 180 |
9.9 |
| 20 |
CGAF-C20 |
12.2 |
| 25 |
CGAF-C25 |
12.0 |
| 30 |
CGAF-C30 |
11.7 |
| 40 |
CGAF-C40 |
12.5 |
| 50 |
CGAF-C50 |
12.1 |
| 60 |
CGAF-C60 |
12.8 |
Notes:
1. Integrated Part Load Values are EERs in (BTU/watt-hour). |
Copyright © 19962009 AECinfo.com
|
|