Trane Company (The)
Air Cooled Liquid Chillers
Air Cooled Liquid Chillers - Page 26
Air Cooled Liquid Chillers
| Electrical Data - 50 Hz 10-60 Hz Table 27-1 Electrical Data
Notes: 1. MCA: Minimum Circuit Ampacity is 125% of the largest compressor RLA plus 100% of the other compressor(s) RLA plus the sum of the condenser fan FLA plus any other load rated at 1AMP or more. 2. Maximum Fuse Size: 225% of the largest compressor RLA plus 100% of the other compressor(s) RLA plus the sum of the condenser fan FLA plus any other load rated at 1 AMP or more. 3. Recommended Dual Element Fuse Size: 150% of the largest compressor RLA plus 100% of the other compressor(s) RLA plus the sum of the condenser fan FLA plus any other load rated at 1 AMP or more. 4. RLA: Rated in accordance with UL standard 1995. 5. Local codes may take precedence. 6. Control kw includes operational controls only. Does not include evaporator heat tape. 7. All units are across the line starting. Compressors will never start simultaneously. 8. One 240/50/1, 5 AMP jobsite provided power connection is required to operate the evaporator heat tape. |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||