| Controls 10, 15
Tons ELECTRICAL
CONTROL SYSTEM
The controls used on CGA 10 and 15-
ton units are classified either as "safety" controls or "operational" controls. Brief descriptions of the specific
safety and operating controls used in the CGA control
scheme are provided in the following paragraphs.
Refer to the following control descriptions for control settings.
UNIT SAFETY CONTROLS
Low Pressure Cutout (LPC01,
LPC02)
Mounted below the unit control box are two low pressure cutouts
that open and stop compressor operation if the
operating pressure drops below 38.5± 1 psig. The cutout automatically resets when
the pressure reaches 44.5 ± 2
psig. The LPCO is a SPDT device. If it opens at low ambient start-up, it will energize ODF relay, stopping the outdoor
fan(s) while the compressor remains energized through
the LAST (Low Ambient Start Timer).
High Pressure Cutout (HPC01,
HPC02)
These units have high pressure cutouts that open and stop compressor operation if the discharge pressure
reaches 400 ± 10 psig. The cutout automatically resets when pressure
drops to 250 + 15 psig.
Reset Relays (RRS, RR2)
If the unit is shut down by the low pressure cutout
(or high pressure cutout), the reset relay locks out
the compressor contactor (CCS, CC2). This prevents
the system from recycling until the condition that caused the low (or high) pressure
cutout to trip is determined and corrected.
CAUTION: To prevent unit damage,
do not reset the control circuit until the cause of the safety lockout is identified and corrected.
To reset RR1 and RR2, open and
reclose the unit disconnect switch.
Low Temperature Cutout (LTC)
The LTC is designed to disable the
unit if the leaving water temperature falls too low. The LTCs remote sensing bulb is mounted at the outlet end of
the evaporator, where it monitors leaving water
temperature.
During normal unit operation, if the
low temperature cutout (LTC) senses a temperature falling to 36°F ± 3.0°F,
the LTC will open to interrupt compressor operation. (Manual reset is
required.)
Motor Overloads These
units have internal compressor and condenser fan motor overloads. These overloads protect the motors from overcurrent and
overheating conditions and automatically reset as soon
as they cool sufficiently.
UNIT OPERATIONAL CONTROLS
Water Temperature Thermostat
(WTT)
System operation for 10 and 15-ton CGA units is governed by a two-stage
water temperature thermostat (WTT). The remote sensing bulb of this device is factory-installed in a bulb well located on the evaporator
water inlet; here, it monitors the temperature of the
water returning to the evaporator.
Low Ambient Start Timer (LAST)
When one of the two timers energizes, the low pressure control is bypassed for four minutes, this allows time
for suction pressure to build sufficiently for the low
pressure cutout contacts to close.
Hot Gas Bypass Timer, Solenoid
(HGBT, HGBS)
The hot gas bypass option is factory-installed only, and is used in a chilled water system to keep the
first stage compressor on-line during short no-load or
light-load conditions. When Water Temperature Thermostat (WTT) first stage opens, 24-volt power is supplied to the Compressor
Contactor (CC1) through Hot Gas Bypass Timer (HGBT)
pins one and four. Power is also applied from WTT-B to HGBT coil (fixed 30- minute time delay pick-up) and to the Hot Gas
Bypass Solenoid (HGBS) through HGBT pins eight and
five. If first stage cooling remains satisfied for
30 minutes, HGBT will energize and shut down the compressor. If there is a call
for cooling during HGBP mode, the unit will return to
cooling mode.
The adjustable hot gas bypass valve
is factory set at 70 psig.
Note: Hot gas bypass is
available only on the lead compressor circuit.
Anti-Short Cycle Timers (ASCT1,
ASCT2)
An anti-short cycle timer is provided in each compressor control circuit to protect the compressors from starting
too frequently. This can occur as a result of just over
0%, or just over 50% of the unit capacity, or because
of sudden power outages of short duration. Whenever the contacts of the water temperature thermostat (WTT) open
or when there is a momentary power outage the
anti-short cycle timer will lock out compressor operation for three minutes.
Delay Between Compressors (DBC)
The delay between compressors prevents both compressors from starting
at the same time by delaying compressor number two for
30 seconds.
Definition of Acronyms
| ASCT |
Anti-Short Cycle Timer |
| CC |
Compressor Contactor |
| CWFIR |
Chilled Water Flow Interlock Relay |
| CWPS |
Chilled Water Pump Starter |
| DBC |
Time Delay Between Compressors |
| HGBT |
Hot Gas Bypass Timer |
| HPCO |
High Pressure Cutout |
| LAST |
Low Ambient Start Timer |
| LPCO |
Low Pressure Cutout |
| LTC |
Low Temperature Cutout |
| ODF |
Outdoor Fan |
| RR |
Reset Relay |
| SPDT |
Single Pole, Double Throw |
| WTT |
Water Temperature Thermostat |
|