Homepage  
Search
find:
search for:
   
 
Site Navigation
News / Publications
Jobs
Service
   Add this page to Google Bookmarks
   Add this page to Mister Wong
   Add this page to del.icio.us
 
   Trane Company (The)  Air Cooled Liquid Chillers  

Air Cooled Liquid Chillers - Page 32

 

 

Controls 20 - 60 Tons Interface

UCM’s response to changing cooling requirements. This value can be set through the HI to allow flexibility in maintaining precise control conditions.

Chiller Freeze Protection

The microprocessor will prevent the evaporator fluid from freezing by reducing chiller capacity, ultimately shutting down all compressors and sending a manually resettable diagnostic. The inputs for freeze protection are the low leaving solution temperature cutout and the leaving solution temperature.

Evaporator Solution Flow Interlock

The IntelliPak controls offer both an internal loss of flow protection, as well as an external evaporator flow switch interlock. Internally, the control algorithm will sense and compare the entering solution temperature and the leaving solution temperature to detect loss of flow during or after start-up. This input to the UCM shall have priority over all other commands and will stop the chiller and a manually resettable diagnostic will result. Additionally, an external field installed flow switch can be wired into the unit terminal strip; this feature can be enabled or disabled. When an open condition is detected for 6 seconds or longer, the chiller will shut down and send a manually resettable diagnostic alarm.

Head Pressure Control Condenser head pressure control is provided in the UCM by staging condenser fans on or off to maintain the saturated condensing temperature. This function will allow cooling operation down to 30°F as standard. Minimum on and off timing is built into the algorithm to prevent rapid cycling.

Pump down

This feature can be enabled or disabled through the Human Interface. When it is enabled, pump down will be initiated prior to shutting down the last capacity stage on each circuit by de-energizing a liquid line solenoid valve. Pump down is terminated by the opening of the low pressure switch, or 30 seconds after the cycle is initiated. On units equipped with hot gas bypass, pump down will be initiated upon termination of the hot gas bypass cycle.

Chiller Solution Pump Control

The UCM has two operating modes for the chiller solution pump control, Auto and On. The UCM additionally has a relay output that will energize/ de-energize the chiller’s solution pump control circuit. The relay is deenergized, stopping the pump, when emergency stop is activated. The solution pump relay is energized to run the pump in the following modes: freeze protection, normal cooling control, low ambient freeze protection, ice building and loop stabilization, and service mode. Modes that will request the pump to stop are ice building complete, ice building delay, unit stop and external auto/stop.

Low Ambient Start Control

Two functions are integrated into the control to allow operation in extreme conditions and still protect the overall system. Low ambient start control will allow compressor operation below 65°F. In order to avoid nuisance tripping, the low pressure control will be bypassed for a period of time. If the low pressure control is still open at the end of the period, the compressor is shut down and the solenoid valve is opened. The loss of refrigerant flow protection is active in this sequence to additionally protect the chiller.

Hot Start Control

A high ambient start sequence will permit only one compressor to operate when the leaving solution temperature is in the user adjustable range of 60-80°F. When the leaving solution temperature falls below this high limit, the second compressor will be active.

Low Ambient Compressor Lockout

This function will lock out the compressor if the outdoor air temperature is below the low ambient compressor lock out temperature setpoint. This setpoint is adjustable at the Human Interface Panel (HI) between 0-60°F. Compressors will be locked out when outdoor air temperatures fall below that selected temperature and will be allowed to start again when the temperature rises 5° F above the setpoint.

Compressor Lead/Lag

Compressor lead/lag is a user-selectable feature through the Human Interface Panel available on all units. When enabled, the algorithm in the UCM will start compressors based upon the least number of starts and/or run time. This feature is not available with the hot gas bypass option.

Emergency Stop Input A binary input is provided on the Unit Control Module (UCM) for installation of field provided switch or contacts for immediate shutdown of all unit functions.

External Auto/Stop A set of contacts or switches can be field installed that will start and stop the chiller.

Demand Limit

The UCM will accept an input from a field installed device which will prevent one or more compressors from operating. The user can select the number of compressors to be turned off.

Optional Control Features

Phase/Voltage Monitoring

This option will detect high and low incoming line voltage. There are three options that the operator can select in response to high or low voltage; no action, information only diagnostic, and auto reset diagnostic which disables all unit functions. The actual voltage will be displayed on the HI. The option will check for phase loss and phase reversal on the main power terminal. If these conditions are detected, the user can select whether to provide an information only diagnostic, or a "shut down the unit" command, displaying a manual diagnostic.

Current Monitoring

This option will measure and average the amp draw of 2 phases of each compressor.

Superheat/Subcooling Option

This option will include the necessary temperature and pressure sensors to measure and calculate the chiller’s superheat and subcooling numbers for each circuit. These temperatures and pressures, along with calculated values of superheat/subcool, will be displayed in the status menu of the Human Interface. No external refrigerant gauges need to be installed on the chiller for the system operator to check out these conditions.

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2009 AECinfo.com