| Application Considerations 

Table A-1 Multipliers to Adjust Vertical Unit Performance
| |
FC Fans |
AF/BI Fans |
| BHP Multiplier |
1.110 |
1.090 |
| RPM Multiplier |
1.035 |
1.025 |
Dual-Path Layout
Dual-path air handler layouts provide two paths for
outdoor air: one for economizer cooling (if used) and
the other for ventilation to specifically address ASHRAE Standard 62-1989s increased minimum outdoor air requirement.
These paths effectively work in parallel, and each is
provided with its own air treatment components (e.g., filters, heating and cooling coils). Like single-path layouts, dual-path designs can incorporate basic outdoor air,
recirculation, exhaust air and energy recovery
functions. See Figure A-8.
Designing an air handler with two outdoor paths rather
than one (i.e., handling ventilation air separately):
Reduces or eliminates reheat requirements while providing an effective
means of dehumidification for loads with low sensible
heat ratios (high latent cooling requirements).
Avoids increasing supply fan static pressure due to high-pressure-drop components in the ventilation air stream
(i.e., increases latent cooling and filtration capacity
without increasing fan size).
Permits downsizing of the ventilation
path components.
Enables compliance with ASHRAE Standard 62s requirement for measuring outdoor (ventilation) airflow without
significantly increasing the first cost of the air
handler.
Provides a cost-effective means to increase ventilation airflow in an existing system.
AHU Arrangements
After schematically organizing the air handler
components in a single- or dual-path layout, the
components or modules must be physically arranged
in a way that fits the space available. Conventional descriptions of air handler
arrangements reflect the means of establishing airflow
through the coil based on its position relative to
the fan. Typically stated, the fan either draws air through a coil located upstream
or blows air through a downstream coil.
The Modular Climate Changer adds another dimension to
air handler arrangements, allowing designers to combine modules by stacking them on top of each other in space-saving configurations
or connecting them together in a side-by-side
arrangement with transition panels.
Careful evaluation of each arrangements
merits is a critical part of the design process.
Draw-Thru or Blow-Thru . . .
Here are four common air handler arrangements, along
with general application considerations for each.
Horizontal Draw-Thru
(Figure A-9) This traditional air handler
arrangement usually results in the longest unit footprint. Accepted system design
practices are generally the only "restrictions"
on its application.
However:
Vertical Draw-Thru
(Figure A-10) Modular Climate Changer air handlers arranged in this manner typically result in a shorter footprint than
horizontal draw-thru units. Vertical coil modules with
either 1 /2 -inch "unit" coils or 5 /8 -inch
"shipping" coils are available; see "AHU
Components: Coil Module." When designing an air
handler in this configuration:
The bottom deck must be longer than the fan module to avoid creating a "cantilever" effect.
Derate fan performance (speed and brake horsepower) if the coil is in the air-turning section of the unit; see Table A-1.
(The Modular Climate Changer selection program does
this automatically.)
|