   Trane Company (The)  Modular Climate Changer  

Modular Climate Changer - Page 32

 

 

Unit Sizes

    H = 24 3 /4 Weights
    W = 31 Single Double
  Module L Wall Wall
A Intake Module 15 1 /2 94 94
B Traq Damper Mixing Box 36 167 215
C Mixing/Filter-Mixing Box1 24 3 /4 167 215
D Economizer 24 3 /4 167 215
E Air Blender 401 /4 160 205
F Open Return Filter 4 8 8
G Flat Filter 11 64 76
H Angled Filter 24 3 /4 103 131
I Bag Filter 36 123 163
J Cartridge Filter 24 3 /4 103 133
K Small Inspection or Blank 11 56 68
L Medium Access or Blank 15 1/2 64 81
N Large Access or Blank 24 3 /4 87 115
O Extra Large Access or Blank 36 105 145
P Turning or Vertical Blank 24 3/4 87 196
Q Small Horizontal Coil 11 55 67
R Medium Horizontal Coil 15 1/2 65 82
T Large Horizontal Coil 24 3/4 86 114
U Vertical Coil 24 3/4 87 196
W Moisture Eliminator 11 68 80
X External Face and Bypass 15 1/2
H = 29 3 /4
102 119
Y Internal Face and Bypass 26 1/2 85 102
Z Face Damper 15 1/2 93 110
AA Horizontal Fan 36
FC Fan
249 289
AB Diffuser 15 1/2 70 87
AC Top-Mounted Discharge Plenum 36
H = 29 3 /4
N/A 145
AD Front-Mounted Discharge Plenum 24 3/4 N/A 119

Fan module weights include largest ODP motor and IGV when applicable. Coil module weights includes the coil module only, add coil weights separately. 1. Filter-mixing box module is 36-inches in length.

Table U-2 — Coil Data

  Area(Ft2) Qty-Size

1/2’’Unit Coils UW, UF

3.32 1-21x23
Shipping Coils
Full 2.75 1-18x22
Custom 3.50 1-18x28
Modified 1.83 1-12x22

Table U-3 — Coil Availability

Module Size 1/2 ’’ Unit Coil Shipping Coils
Small 2 Row 1-2 Row
Medium 2-8Row 1-4 Row
Large N/A 1-10 Row
Vertical 2-8 Row 1-6 Row

Table U-4 — 1 /2 ’’ Unit Coil Water Connection Sizes (Inches)

  UW
Header Height 21
Supply 1 1/2
Return 1 1/2
Drain & Vent 3/8

Shipping Coil connections are located on page 64. See pages 64-73 for Refrigerant Coil Connections and Circuiting.

Table U-5 — Filter Data

  Area(Ft2) Qty-Size
2’’,4’’Flat
(TA, permanent, pleated media)
3.5 20x25
Angled
(TA, permanent, pleated media)
5.6 2-16x25
Bag/Cartridge
(65%, 85% or 95% Efficiency)
3.3 20x24

Refer to page 78 for filter pressure drops.

Table U-6 — Areas

Traq Damper Mixing Box,  
Mixing Box or Economizer

Traq Damper

Air foil Blade Damper

 
0.92
1.78
Internal Face and Bypass

Face Area

Bypass Area

 
0.95
0.95
External Face and Bypass

Face Area

Bypass Area

 
2.84
1.89
Face Damper 2.84
Air Blender 1.46

Refer to pages 74-79 for pressure drops. See Table P-14 on page 79 for damper torque requirements.

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2009 AECinfo.com