   Trane Company (The)  Modular Climate Changer  

Modular Climate Changer - Page 34

 

 

Unit Sizes     Size 06

    H = 27 1/4 Weights
    W = 44 Single Double
  Module L Wall Wall
A IntakeModule 15-1/2 124 124
B TraqDamperMixingBox 27-1/4 194 232
C Mixing/Filter-MixingBox 27-1/4 194 232
D Economizer 27-1/4 194 232
E AirBlender 42-3/4 201 262
F OpenReturnFilter 4 13 13
G FlatFilter 11 80 96
H AngledFilter 27-1/4 135 174
I BagFilter 41 164 223
J CartridgeFilter 27-1/4 164 175
K SmallInspectionorBlank 11 67 83
L MediumAccessorBlank 15-1/2 77 99
N LargeAccessorBlank 27-1/4 112 151
O ExtraLargeAccessorBlank 41 140 199
P TurningorVerticalBlank 27-1/4 112 256
Q SmallHorizontalCoil 11 68 84
R MediumHorizontalCoil 15-1/2 81 103
T LargeHorizontalCoil 27-1/4 114 153
U VerticalCoi 27-1/4 112 256
W MoistureEliminator 11 91 107
X ExternalFaceandBypass 15 1/2
H = 32-1/4
136 158
Y InternalFaceandBypass 26-1/2 115 137
Z FaceDamper 15-1/2 121 143
AA HorizontalFan 41
FC Fan
373 446
AB Diffuser 15-1/2 87 109
AC Top-MountedDischargePlenum 41
H = 27-1/4
N/A 209
AD Front-MountedDischargePlenum 27-1/4 N/A 163
AE Multizone/DoubleDuct 46-1/2
H = 4-1/2
362 435

Fan module weights include largest ODP motor and IGV when applicable. Coil module weights includes the coil module only, add coil weight separately.

Table U-8 — Coil Data

Area (Ft2) Qty-Size
1/2’’ Unit Coils   UW, UF 5.86 1-23x36
Shipping Coils 
Full
4.38 1-18x35
Custom 5.13 1-18x41
Modified 2.92 1-12x35
HotDeck 2.90 1-12x35

Table U-9 — Coil Availability

Module Size 1/2’’ Unit Coil Shipping Coils
Small 2 Row 1-2 Row
Medium 2-8 Row 1-4 Row
Large N/A 1-10 Row
Vertical 2-8 Row 1-6 Row
Multizone    
Cold Deck 2-8 Row 1-4 Row
Hot Deck N/A 1-2 Row

Table U-10 — 1 /2 ’’ Unit Coil Water Connection Sizes (Inches)

  UW
Header Height 23
Supply 1-1/2
Return 1-1/2
Drain&Vent 3/8

Shipping Coil connections are located on page 64. See pages 64-73 for Refrigerant Coil Connections and Circuiting.

Table U-11 — Filter Data

  Area(Ft2) Qty-Size
2’’,4’’Flat
(TA, permanent, pleated media)
5.6 2-20x20
Angled
(TA, permanent, pleated media)
8.9 4-16x20
Bag/Cartridge
(65%, 85% or 95% Efficiency)
5.6 2-20x20

Refer to page 78 for filter pressure drops.

Table U-12 — Areas

  Area(Ft2)
Traq Damper Mixing Box,  
Mixing Box or Economizer  

Traq Damper

1.84

Airfoil Blade Damper

3.07
Internal Face and Bypass  

Face Area

1.44

Bypass Area

1.44
External Face and Bypass  

Face Area

4.33

Bypass Area

2.88
Face Damper 4.33
Multizone(per deck) 2.64
(Max.zones/deck) 6
Air Blender 2.28

Refer to pages 74-79 for pressure drops. See Table P-14 on page 79 for damper torque requirements.

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2009 AECinfo.com