| Unit Sizes
Size 06 
| |
|
H = 27 1/4 |
Weights |
| |
|
W = 44 |
Single |
Double |
| |
Module |
L |
Wall |
Wall |
| A |
IntakeModule |
15-1/2 |
124 |
124 |
| B |
TraqDamperMixingBox |
27-1/4 |
194 |
232 |
| C |
Mixing/Filter-MixingBox |
27-1/4 |
194 |
232 |
| D |
Economizer |
27-1/4 |
194 |
232 |
| E |
AirBlender |
42-3/4 |
201 |
262 |
| F |
OpenReturnFilter |
4 |
13 |
13 |
| G |
FlatFilter |
11 |
80 |
96 |
| H |
AngledFilter |
27-1/4 |
135 |
174 |
| I |
BagFilter |
41 |
164 |
223 |
| J |
CartridgeFilter |
27-1/4 |
164 |
175 |
| K |
SmallInspectionorBlank |
11 |
67 |
83 |
| L |
MediumAccessorBlank |
15-1/2 |
77 |
99 |
| N |
LargeAccessorBlank |
27-1/4 |
112 |
151 |
| O |
ExtraLargeAccessorBlank |
41 |
140 |
199 |
| P |
TurningorVerticalBlank |
27-1/4 |
112 |
256 |
| Q |
SmallHorizontalCoil |
11 |
68 |
84 |
| R |
MediumHorizontalCoil |
15-1/2 |
81 |
103 |
| T |
LargeHorizontalCoil |
27-1/4 |
114 |
153 |
| U |
VerticalCoi |
27-1/4 |
112 |
256 |
| W |
MoistureEliminator |
11 |
91 |
107 |
| X |
ExternalFaceandBypass |
15 1/2
H = 32-1/4 |
136 |
158 |
| Y |
InternalFaceandBypass |
26-1/2 |
115 |
137 |
| Z |
FaceDamper |
15-1/2 |
121 |
143 |
| AA |
HorizontalFan |
41
FC Fan |
373 |
446 |
| AB |
Diffuser |
15-1/2 |
87 |
109 |
| AC |
Top-MountedDischargePlenum |
41
H = 27-1/4 |
N/A |
209 |
| AD |
Front-MountedDischargePlenum |
27-1/4 |
N/A |
163 |
| AE |
Multizone/DoubleDuct |
46-1/2
H = 4-1/2 |
362 |
435 |
Fan module weights include largest
ODP motor and IGV when applicable. Coil module weights includes the coil module only, add coil weight separately.
Table U-8 Coil
Data
| Area |
(Ft2) |
Qty-Size |
| 1/2 Unit Coils
UW, UF |
5.86 |
1-23x36 |
Shipping Coils
Full |
4.38 |
1-18x35 |
| Custom |
5.13 |
1-18x41 |
| Modified |
2.92 |
1-12x35 |
| HotDeck |
2.90 |
1-12x35 |
Table U-9 Coil Availability
| Module Size |
1/2 Unit Coil |
Shipping Coils |
| Small |
2 Row |
1-2 Row |
| Medium |
2-8 Row |
1-4 Row |
| Large |
N/A |
1-10 Row |
| Vertical |
2-8 Row |
1-6 Row |
| Multizone |
|
|
| Cold Deck |
2-8 Row |
1-4 Row |
| Hot Deck |
N/A |
1-2 Row |
Table U-10 1 /2
Unit Coil Water Connection
Sizes (Inches)
| |
UW |
| Header Height |
23 |
| Supply |
1-1/2 |
| Return |
1-1/2 |
| Drain&Vent |
3/8 |
Shipping Coil connections are located
on page 64. See pages 64-73
for Refrigerant Coil Connections and Circuiting.
Table U-11
Filter Data
| |
Area(Ft2) |
Qty-Size |
2,4Flat
(TA, permanent, pleated media) |
5.6 |
2-20x20 |
Angled
(TA, permanent, pleated media) |
8.9 |
4-16x20 |
Bag/Cartridge
(65%, 85% or 95% Efficiency) |
5.6 |
2-20x20 |
Refer to page
78 for filter pressure drops.
Table U-12 Areas
| |
Area(Ft2) |
| Traq Damper Mixing Box, |
|
| Mixing Box or Economizer |
|
Traq Damper |
1.84 |
Airfoil Blade Damper |
3.07 |
| Internal Face and Bypass |
|
Face Area |
1.44 |
Bypass Area |
1.44 |
| External Face and Bypass |
|
Face Area |
4.33 |
Bypass Area |
2.88 |
| Face Damper |
4.33 |
| Multizone(per deck) |
2.64 |
| (Max.zones/deck) |
6 |
| Air Blender |
2.28 |
Refer to pages 74-79
for pressure drops. See Table P-14 on page 79 for damper torque
requirements. |