| Search |
|
|
|
| |
| Site Navigation |
|
|
|
| News / Publications |
|
|
|
| Jobs | |
|
|
| Service |
|
|
|
|
|


|
| |
|
| |
Trane Company (The) Modular Climate Changer Modular Climate Changer - Page 35
| Unit Sizes Size 08 







Table U-13 Fan Data
| |
Fan Type |
| |
A |
B |
| Design CFM |
3770 |
3770 |
| Size/Type |
13-1/2 FC |
12-1/4 FC |
| Max TSP/RPM |
2.5/1273 |
5.0/2027 |
| Bearing Size (Inches) |
|
Drive Side |
1 |
1-3/16 |
OppositeDriveSide |
1 |
1-3/16 |
| Shaf tSize (Inches) |
1 |
1-3/16 |
| Outlet Area (FT2) |
2.31 |
1.90 |
| Motor HP Range |
1/2-5 |
1-71/2 |
| IGV |
Torque |
(Inch-Lb.) |
| 2000 FPM (4.0 WC) |
10.9/3.9 |
10.0/3.5 |
| 3000 FPM (Max. RPM & BHP) |
24.5/8.7 |
22.5/7.8 |
Torques are shown for Open/Closed
operation at 2000 and 3000 FPM fan
outlet velocity. |
Copyright © 19962009 AECinfo.com
|
|