| Unit Sizes
Size 08 
| |
|
H = 31 |
Weights |
| |
|
W = 48 |
Single |
Double |
| |
Module |
L |
Wall |
Wall |
| A |
Intake Module |
15-1/2 |
141 |
142 |
| B |
Traq Damper Mixing Box |
31 |
237 |
286 |
| C |
Mixing/Filter-Mixing Box |
31 |
237 |
286 |
| D |
Economizer |
31 |
237 |
286 |
| E |
Air Blender |
46-1/2 |
233 |
307 |
| F |
Open Return Filter |
4 |
14 |
14 |
| G |
Flat Filter |
11 |
87 |
105 |
| H |
Angled Filter |
31 |
158 |
207 |
| I |
Bag Filter |
44 |
188 |
258 |
| J |
Cartridge Filter |
31 |
188 |
210 |
| K |
Small Inspection or Blank |
11 |
73 |
91 |
| L |
Medium Access or Blank |
15-1/2 |
85 |
110 |
| N |
Large Access or Blank |
31 |
134 |
183 |
| O |
Extra Large Access or Blank |
44 |
161 |
231 |
| P |
Turning or Vertical Blank |
31 |
134 |
298 |
| Q |
Small Horizont Coil |
11 |
74 |
92 |
| R |
Medium Horizontal Coil |
15-1/2 |
88 |
113 |
| T |
Large Horizontal Coil |
31 |
136 |
185 |
| U |
Vertical Coil |
31 |
134 |
298 |
| W |
Moisture Eliminator |
11 |
105 |
123 |
| X |
External Face and Bypass |
15-1/2
H=36 |
163 |
188 |
| Y |
Internal Face and Bypass |
15-1/2 |
129 |
154 |
| Z |
Face Damper |
15-1/2 |
147 |
172 |
| AA |
Horizontal Fan |
44 FC Fan |
447 |
542 |
| AB |
Diffuser |
15-1/2 |
96 |
121 |
| AC |
Top-Mounted Discharge Plenum |
44
H = 31 |
N/A |
236 |
| AD |
Front-Mounted Discharge Plenum |
31 |
N/A |
198 |
| AE |
Multizone/Double Duct |
461-/2
H=48 |
392 |
474 |
Fan module weights include largest
ODP motor and IGV when applicable. Coil module weights includes the coil module only, add
coil weights separately.
Table U-14 Coil Data
| |
Area(Ft2) |
Qty-Size |
| 1/2 Unit Coils UW, UF |
7.54 |
1-27x40 |
| Shipping Coils Full |
6.50 |
1-24x39 |
| Custom |
7.50 |
1-24x45 |
| Modified |
4.88 |
1-18x39 |
| HotDeck |
3.30 |
1-12x39 |
Table U-15 Coil Availability
| Module Size |
1/2UnitCoil |
Shipping Coils |
| Small |
2 Row |
1-2 Row |
| Medium |
2-8 Row |
1-4 Row |
| Large |
N/A |
1-10 Row |
| Vertical |
2-8 Row |
1-6 Row |
| Multizone |
Cold Deck |
2-8 Row |
1-4 Row |
Hot Deck |
N/A |
1-2 Row |
Table U-16 1 /2
Unit Coil Water Connection Sizes (Inches)
|
UW |
| Header Height |
27 |
| Supply |
1-1/2 |
| Return |
1-1/2 |
| Drain & Vent |
3/8 |
Shipping Coil connections are located
on page 64. See pages 64-73 for
Refrigerant Coil Connections and Circuiting.
Table U-17
Filter Data
| |
Area(Ft2) |
Qty-Size |
| 2,4Flat (TA,
permanent, pleated media) |
6.9 |
2-20x25 |
| Angled (TA, permanent, pleated media) |
11.1 |
4-20x20 |
| Bag/Cartridge (65%,85% or 95% Efficiency) |
6.7 |
2-20x24 |
Refer to page 78
for filter pressure drops.
Table U-18 Areas
| |
Area (Ft2) |
| Traq Damper Mixing Box, Mixing Box or
Economizer |
|
Traq Damper |
1.84 |
Airfoil Blade Damper |
3.46 |
| Internal Face and Bypass |
|
Face Area |
3.19 |
Bypass Area |
1.59 |
| External Face and Bypass |
|
| Face Area |
6.38 |
| Bypass Area |
3.19 |
| Face Damper |
6.38 |
| Multizone (per deck) |
3.07 |
| (Max. zones/deck) |
7 |
| Air Blender |
2.76 |
Refer to pages 74-79
for pressure drops. See Table P-14 on page 79
for damper torque requirements. |