   Trane Company (The)  Modular Climate Changer  

Modular Climate Changer - Page 38

 

 

Unit Sizes         Size 10

    H = 34 Weights
    W = 60 Single Double
  Module L Wall Wall
A Intake Module 15-1/2 187 210
B Traq Dampe rMixing Box 34 325 389
C Mixing/Filter-Mixing Box 34 325 389
D Economizer 34 325 389
E Air Blender 49-1/2 299 393
F Open Return Filter 4 25 25
G Flat Filter 11 113 134
H Angled Filter 24-1/2 161 198
I Bag Filter 34 216 280
J Cartridge Filter 24-1/2 173 210
K Small Inspection or Blank 11 87 108
L Medium Access or Blank 15-1/2 104 134
M Medium Large Access or Blank 24-1/2 129 166
N Large Access or Blank 34 172 236
O Extra Large Access or Blank 34 172 236
P Turning or Vertical Blank 34 172 411
Q Small Horizontal Coil 11 94 115
R Medium Horizontal Coil 15-1/2 112 142
S Medium Large Horizontal 24-1/2 125 188
T Large Horizontal Coil 34 194 258
U Vertical Coil 34 172 411
V Coil w/Access 24-1/2 540 603
W Moisture Eliminator 11 163 184
X External Face and Bypass 15-1/2
H = 39
211 241
Y Internal Face and Bypass 15-1/2 184 214
Z Face Damper 15-1/2 183 213
AA Horizontal Fan 34
FC Fan 514 589
BI Fan 669 744
AB Diffuser 15-1/2 111 141
AC Top-Mounted Discharge Plenum 34 N/A 274
  H = 34  
AD Front-Mounted Discharge Plenum 34 N/A 274
AE Multizone/Double Duct 46-1/2 485 583
  H = 53  

Fan module weights include largest ODP motor and IGV when applicable. Coil module weights includes the coil module only, add coil weights separately.

Table U-20 — Coil Data

  Area (Ft2) Qty-Size
1/2’’ UnitCoils UW, UF 9.64 1-27x51
Shipping Coils Full 8.33 1-24x50
Custom 9.50 1-24x57
Modified 6.25 1-18x50
HotDeck 6.30 1-18x50

Table U-21 — Coil Availability

Module Size 1/2’’ Unit Coil Shipping Coils
Small 2 Row 1-2 Row
Medium 2-8 Row 1-4 Row
Medium Large

Coil

N/A 1-8 Row

Coil w/Access

2-8 Row 1-4 Row
Vertical 2-8 Row 1-6 Row
Multizone

Cold Deck

2-8 Row 1-4 Row

Hot Deck

N/A 1-2 Row

Table U-22 — 1 /2 ’’ Unit Coil Water Connection Sizes (Inches)

  UW
HeaderHeight 27
Supply 1-1/2
Return 1-1/2
Drain&Vent 3/8

Shipping Coil connections are located on page 64. See pages 64-73 for Refrigerant Coil Connections and Circuiting.

Table U-23 — Filter Data

  Area (Ft2) Qty-Size
2’’,4’’Flat (TA, permanent, pleated media) 9.7 2-20x25
    1-16x25
Angled (TA, permanent, pleated media) 13.9 4-20x25
Bag/Cartridge 9.3 3-12x24
(65%,85% or 95% Efficiency)   1-20x24

Refer to page 78 for filter pressure drops.

Table U-24 — Areas

  Area (Ft2)
Traq Damper Mixing Box, Mixing Box or Economizer  

Traq Damper

2.77

Airfoil Blade Damper

7.71
Internal Face and Bypass  

Face Area

6.16

Bypass Area

2.05
External Face and Bypass  

Face Area

8.21

Bypass Area

4.11
Face Damper 8.21
Multizone (per deck) 4.98
(Max. zones/deck) 9
Air Blender

3.86

Refer to pages 74-79 for pressure drops. See Table P-14 on page 79 for damper torque requirements.

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2009 AECinfo.com