Standard CenTraVac® Features The following features are provided as standard with all Trane CenTraVac® chillers:
Cen TraVac Motor The motor provided in the Trane CenTraVac chiller is a specially designed squirrel cage, two pole induction motor suitable for 50 and 60 hertz, three-phase current. Trane CenTraVac motors are cooled by liquid refrigerant surrounding the motor windings and rotor. Use of liquid refrigerant results in uniform low temperatures throughout the motor, thereby promoting long motor life. Oil Pump Motor The oil pump motor is a 120 volt, 50/60 hertz, 1 /4 hp, 1 phase motor with protective fusing and panel mounted contactor. Purge The purge unit motor is a 120 volt, 50/60 hertz, 1 /4 hp, 1 phase motor with integral overload protection and panel mounted contactor. The use of an air-cooled condensing unit obtains separation temperatures in the purge drum as low as 0 F. Normal operating efficiency does not exceed 0.002 lbs. of refrigerant lost per pound of dry air removed. The purge system can be operated at any time, independent of chiller operation. Optional Features Trane offers a selection of optional features to either complete the basic chiller installation or to allow modification for special purpose applications.
Compressor Motor Starting Equipment Features To eliminate the need for special engineering design and multiple vendor coordination, Trane can provide compressor motor starting equipment built to rigid Trane specifications. The types of starters available include: Low Voltage (200 to 600 volts)
Medium Voltage (2300 to 6000 Volts)
Medium voltage starters are provided as standard with a non-load break isolation switch and current limiting fuses. All starters provided by Trane include the following standard features for safe, efficient application and ease of installation:
In addition, Trane offers a wide selection of optional starter features.
If the CenTraVac compressor starting equipment is provided by others, the starter must be designed in accordance with the current Trane standard engineering specification "Water- Cooled CenTraVac® Starter Specification." It is also recommended that two copies of the interconnecting and control circuit wiring diagrams be forwarded to The Trane Company for review. This service is provided at no charge, and is intended to help minimize the possibility that Trane CenTraVac chillers will be applied in improper starting and control systems. However, the responsibility for providing proper starting and control systems must remain with the system designer and the installer. Contact your local Trane sales office for further information. |