Homepage  
Search
find:
search for:
   
 
Site Navigation
News / Publications
Jobs
Service
   Add this page to Google Bookmarks
   Add this page to Mister Wong
   Add this page to del.icio.us
 
   Trane Company (The)  CenTraVac Liquid Chillers - 11/97  

CenTraVac Liquid Chillers - 11/97 - Page 24

 

 

ctv1n24a.gif (1738 bytes)

Application Considerations

Condenser Water Limitations Trane CenTraVac® chillers start and operate over a range of load conditions with controlled water temperatures. Reducing the condenser water temperature is an effective method of lowering the chiller power input. However, the effect of lowering the condenser water temperature may cause an increase in system power consumption.

In many applications Trane CenTraVac chillers can start and operate without control of the condenser water temperature. However, for optimum system power consumption, and for any applications with multiple chillers, control of the condenser water circuit is recommended. Integrated control of the chillers, pumps and towers is easily accomplished with Trane’s UCP2 and/ or Tracer system.

Chillers are designed to ARI conditions of 85 F, but Trane CenTraVac chillers can operate to a five psig pressure differential between the condenser and evaporator at any steady state load without oil loss, oil return, motor cooling, refrigerant hang-up or purge problems. And this differential can equate to safe minimum entering condenser water temperatures at or below 55 F, dependent on a variety of factors such as load, leaving evaporator temperature and component combinations. Start-up below this differential is possible as well, especially with UCP2 soft start features. Contact your local Trane Sales Office for applications information regarding optimum condenser water temperatures for a specific application.

Water Treatment

The use of untreated or improperly treated water in a chiller may result in scaling, erosion, corrosion, algae or slime. It is recommended that the services of a qualified water treatment specialist be used to determine what treatment, if any, is advisable. The Trane Company assumes no responsibility for the results of untreated, or improperly treated water.

Water Pumps

Avoid specifying or using 3600 rpm condenser and chilled water pumps. Such pumps may operate with objectionable noises and vibrations. In addition, a low frequency beat may occur due to the slight difference in operating rpm between water pumps and CenTraVac motors. Where noise and vibration-free operation are important, The Trane Company encourages the use of 1750 rpm pumps.

Electrical Information

Minimum Circuit Ampacity

To properly size field electrical wiring, the electrical engineer or contractor on a project needs to know the minimum circuit ampacity of the CenTraVac® machine. The National Electrical Code (NEC), in Article 440-33, defines the method of calculating the minimum circuit ampacity. The minimum circuit ampacity is defined as the sum of two amperages: 125 percent of the compressor motor Rated Load Amps (RLA), plus the Full Load Amps (FLA) of all remaining loads on the same circuit. For starter to motor wiring, there are no other remaining loads. For main power supply to the starter, there is a remaining load consisting of the 3 KVA control power transformer which supplies power to the controls, the oil pump motor, oil sump heater and the purge unit motor. Therefore, the remaining load FLA equals 3000 divided by the unit design voltage. Application Considerations

As an example, calculate the minimum circuit ampacity of a machine which has a design RLA of 350 amps and is to be operated on a 460 volt power supply:

Minimum Circuit Ampacity = 3000 VA (125% x 350 Amps) +  460 V

=

437.5 Amps + 6.5 Amps

=

444 Amps

After the minimum circuit ampacity has been determined, the electrical engineer or contractor will refer to the appropriate conductor sizing table in the NEC to determine the exact conductors required. A typical table for 75 F conductors is included in the Trane submittal. The selection of conductors is based on a number of jobsite conditions (i.e. type of conductor, number of conductors, length of conductors, ambient temperature rating of conductors).

Branch-Circuit Short-Circuit and Ground Fault Protection

Circuit breakers and fused disconnects should be sized by the electrical engineer or contractor in strict accordance with NEC Article 440-21 and in accordance with all local codes. This protection should be for motor type loads and should not be less than 150 percent of the compressor motor rated load amps (RLA).

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2009 AECinfo.com