 |
Application Considerations |
Condenser Water Limitations Trane CenTraVac® chillers start and operate over
a range of load conditions with controlled water
temperatures. Reducing the condenser water temperature is an effective method of lowering the chiller power input. However, the
effect of lowering the condenser water temperature may
cause an increase in system power consumption.
In many applications Trane CenTraVac chillers can start and operate without control of the condenser water temperature.
However, for optimum system power consumption, and for
any applications with multiple chillers, control of the condenser water circuit is recommended. Integrated control of the
chillers, pumps and towers is easily accomplished with
Tranes UCP2 and/ or Tracer system.
Chillers are designed to ARI conditions of 85 F, but Trane CenTraVac chillers can operate to a five psig pressure differential
between the condenser and evaporator at any steady
state load without oil loss, oil return, motor cooling, refrigerant hang-up or purge problems. And this differential can equate to
safe minimum entering condenser water temperatures at
or below 55 F, dependent on a variety of factors such as load, leaving evaporator
temperature and component combinations. Start-up
below this differential is possible as well, especially with UCP2 soft start features. Contact your local Trane Sales Office
for applications information regarding optimum
condenser water temperatures for a specific
application.
Water Treatment
The use of untreated or improperly treated water in a chiller may result in scaling, erosion, corrosion, algae or slime.
It is recommended that the services of a qualified
water treatment specialist be used to determine what
treatment, if any, is advisable. The Trane Company assumes no responsibility for
the results of untreated, or improperly treated water.
Water Pumps
Avoid specifying or using 3600 rpm condenser and chilled water pumps. Such pumps may operate with objectionable
noises and vibrations. In addition, a low frequency
beat may occur due to the slight difference in operating rpm between water pumps and
CenTraVac motors. Where noise and vibration-free
operation are important, The Trane Company encourages the use of 1750 rpm pumps.
Electrical Information
Minimum Circuit Ampacity
To properly size field electrical wiring, the electrical engineer or contractor on a project needs to know the minimum circuit
ampacity of the CenTraVac® machine. The National Electrical Code (NEC), in Article 440-33, defines the method
of calculating the minimum circuit ampacity. The
minimum circuit ampacity is defined as the sum of two
amperages: 125 percent of the compressor motor Rated Load Amps (RLA), plus
the Full Load Amps (FLA) of all remaining loads on the
same circuit. For starter to motor wiring, there are no
other remaining loads. For main power supply to the starter, there is a remaining
load consisting of the 3 KVA control power transformer
which supplies power to the controls, the oil pump motor, oil sump heater and the purge unit motor. Therefore, the remaining
load FLA equals 3000 divided by the unit design
voltage. Application Considerations
As an example, calculate the minimum circuit ampacity of a machine which has a design RLA of 350 amps and is to be
operated on a 460 volt power supply:
| Minimum Circuit Ampacity = |
3000 VA (125% x 350 Amps) + 460 V |
= |
437.5 Amps + 6.5 Amps |
= |
444 Amps |
After the minimum circuit ampacity has been determined, the electrical engineer
or contractor will refer to the appropriate conductor
sizing table in the NEC to determine the exact conductors required. A typical table for 75 F conductors is included in the Trane submittal.
The selection of conductors is based on a number of
jobsite conditions (i.e. type of conductor, number of conductors, length of conductors,
ambient temperature rating of conductors).
Branch-Circuit Short-Circuit and Ground Fault Protection
Circuit breakers and fused disconnects should be sized by the electrical engineer
or contractor in strict accordance with NEC Article
440-21 and in accordance with all local codes. This protection should be for motor type loads and should not be less than 150
percent of the compressor motor rated load amps (RLA). |