Trane Company (The) CenTraVac Liquid Chillers - 11/97 CenTraVac Liquid Chillers - 11/97 - Page 38
 |
Physical Dimensions 50
Hz Units |


CL1 CAN BE AT EITHER END OF MACHINE AND IS REQUIRED
FOR TUBE PULL CLEARANCE.CL2 IS ALWAYS AT THE OPPOSITE END OF MACHINE FROM CL1 AND IS
REQUIRED FOR SERVICE CLEARANCE.
| ENGLISH
UNITS |
|
Envolpe |
Clearance |
Unit
Dimensions |
|
COMP |
Shell
Size |
Shell
Arange-
ment |
|
W/O Unit Mounted
Starters |
With Unit Mounted
Starter |
Tube pull |
|
|
|
W/O Unit Mounted
Starters |
With Unit Mounted
Starter |
| EL |
EW |
EW |
CL1 |
CL2 |
Lenght |
Height |
Width |
Width |
C
V
H
E |
190-270 |
320 |
SS |
26' 5" |
10' 6- 1/4" |
11'4-1/2" |
11' 9" |
3' 5" |
11' 3" |
7' 3-3/4" |
5' 9-1/4" |
6' 7-1/2" |
| 190-270 |
320 |
SL&LL |
33' 11-1/4" |
10' 6- 1/4" |
11' 4-1/2" |
15' 6" |
3' 5" |
15' 0-1/4" |
7' 3-3/4" |
5' 9-1/4" |
6' 7-1/2" |
| 190-270 |
500 |
SS |
26' 6-3/8" |
11'4- 5/8" |
12' 6-7/8" |
11' 9" |
3' 6-3/8" |
11' 3" |
7' 10-3/4" |
6' 7-5/8" |
7' 9-7/8" |
| 190-270 |
500 |
SL&LL |
34' 0-5/8" |
11'4- 5/8" |
12' 6-7/8" |
15' 6" |
3' 6'-3/8" |
15' 0-1/4" |
7' 10-3/4" |
6' 7-5/8" |
7' 9-7/8" |
| 300-420 |
500 |
SS |
26' 6-3/8" |
11'4- 5/8" |
12'5-1/2" |
11' 9" |
3' 6-3/8" |
11' 3" |
7' 11" |
6' 7-5/8" |
7' 8-1/2" |
| 300-420 |
500 |
SL&LL |
34' 0-5/8" |
11'4- 5/8" |
12'5-1/2" |
15' 6" |
3' 6-3/8" |
15' 0-1/4" |
7' 11" |
6' 7-5/8" |
7' 8-1/2" |
| 300-420 |
800 |
SS |
27' 4-1/4" |
12' 5- 1/4" |
13'4-5/8" |
11' 9" |
4' 4-1/4" |
11' 3" |
9' 6-3/8" |
7' 11-1/4" |
8' 7-5/8" |
| 300-420 |
800 |
SL&LL |
34' 10-1/2" |
12' 5- 1/4" |
13'4-5/8" |
15' 6" |
4' 4-1/4" |
15' 0-1/4" |
9' 6-3/8" |
7' 11-1/4" |
8' 7-5/8" |
C
V
H
G |
480-565 |
500 |
SS |
26' 6-3/8" |
11'4- 5/8" |
12'5-3/4" |
11' 9" |
3' 6-3/8" |
11' 3" |
8' 3-3/4" |
6' 7-5/8" |
7' 8-3/4" |
| 480-565 |
500 |
SL&LL |
34' 0-5/8" |
11'4- 5/8" |
12'5-3/4" |
15' 6" |
3' 6-3/8" |
15' 0-1/4" |
8' 3-3/4" |
6' 7-5/8" |
7' 8-3/4" |
| 480-565 |
800 |
SS |
27' 4-1/4" |
12'5- 1/4" |
13'4-5/8" |
11' 9" |
4' 4-1/4" |
11' 3" |
9' 8" |
7' 11-1/4" |
8' 7-5/8" |
| 480-565 |
800 |
SL&LL |
34' 10-1/2" |
12'5- 1/4" |
13'4-5/8" |
15' 6" |
4' 4-1/4" |
15' 0-1/4" |
9' 8" |
7' 11-1/4" |
8' 7-5/8" |
| 670-780 |
800 |
SS |
27' 4-1/4" |
12' 10" |
13'10-3/4" |
11' 9" |
4' 4-1/4" |
11' 3" |
9' 6-3/4" |
8' 4" |
9' 1-3/4" |
| 670-780 |
800 |
SL&LL |
34' 10-1/2" |
12' 10 |
13'10-3/4" |
15' 6" |
4' 4-1/4" |
15' 0-1/4" |
9' 6-3/4" |
8' 4" |
9' 1-3/4" |
| 670-780 |
800 |
ML&LL |
35' 5-1/4" |
14'5- 3/4 |
15'0-7/8" |
15' 6" |
4 '11" |
15' 0-1/4" |
10' 1-1/8" |
9' 11-3/4" |
10' 3-7/8" |
| 920-1067 |
1420 |
ML&LL |
35' 5-1/4" |
14'5- 3/4 |
15'0-7/8" |
15' 6" |
4 '11" |
15' 0-1/4" |
10' 1-1/8" |
9' 11-3/4" |
10' 3-7/8" |
|
920-1067 |
2100 |
LL |
35' 5-1/4" |
15' 3-3/4 |
15'7 |
15' 6" |
4 '11" |
15' 0-1/4 |
11' 0-7/8" |
10' 9-3/4" |
10' 10" |
|
CL1 CAN BE AT EITHER END OF MACHINE AND IS REQUIRED FOR
TUBE PULL CLEARANCE.
CL2 IS ALWAYS AT THE END OF MACHINE FROM CL1 AND IS REQUIRED FOR SERVICE CLEARANCE.
| CENTRAVAC WATER
CONNECTION PIPE SIZE |
| Water |
Shell Size |
| Passes |
032 |
050 |
080 |
142 |
210 |
| EVAPORATOR |
Nominal Pipe Size
(Inches) |
| 1 PASS |
8 |
10 |
12 |
16 |
16 |
| 2 PASS |
6 |
8 |
10 |
12 |
14 |
| 3 PASS |
5 |
6 |
8 |
10 |
12 |
| CONDENSER 2 PASS |
6 |
8 |
10 |
12 |
14 |
|