| Search |
|
|
|
| |
| Site Navigation |
|
|
|
| News / Publications |
|
|
|
| Jobs | |
|
|
| Service |
|
|
|
|
|


|
| |
|
| |
Trane Company (The) CenTraVac Liquid Chillers - 11/97 CenTraVac Liquid Chillers - 11/97 - Page 39
Physical Dimensions
50 Hz Units


| METRIC UNITS |
|
|
|
|
|
Envelop |
Clearance |
Unit Dimensions |
|
COMP |
Shell Size |
Shell Arrangement |
|
W/O Uint
Mounted Starters |
With Uint Mounted
Starters |
|
|
|
W/O Uint
Mounted Starters |
With Uint Mounted
Starters |
| Tube Pull |
| EL |
EW |
EW |
CL1 |
CL2 |
Length |
Height |
Width |
Width |
| C V
H
E |
190-270 |
320 |
SS |
8052 |
3207 |
3467 |
3581 |
1041 |
3429 |
2229 |
1759 |
2019 |
| 190-270 |
320 |
SL & LL |
10344 |
3207 |
3467 |
4724 |
1041 |
4578 |
2229 |
1759 |
2019 |
| 190-270 |
500 |
SS |
8087 |
3470 |
3832 |
3581 |
1076 |
3429 |
2407 |
2022 |
2384 |
| 190-270 |
500 |
SL & LL |
10379 |
3470 |
3832 |
4724 |
1076 |
4578 |
2407 |
2022 |
2384 |
| 300-420 |
500 |
SS |
8087 |
3470 |
3797 |
3581 |
1076 |
3429 |
2413 |
2022 |
2350 |
| 300-420 |
500 |
SL & LL |
10379 |
3470 |
3797 |
4724 |
1076 |
4578 |
2413 |
2022 |
2350 |
| 300-420 |
800 |
SS |
8338 |
3867 |
4080 |
3581 |
1327 |
3429 |
2905 |
2419 |
2632 |
| 300-420 |
800 |
SL & LL |
10630 |
3867 |
4080 |
4724 |
1327 |
4578 |
2905 |
2419 |
2632 |
| C V
H
G |
480-565 |
500 |
SS |
8087 |
3470 |
3804 |
3581 |
1076 |
3429 |
2534 |
2022 |
2356 |
| 480-565 |
500 |
SL & LL |
10379 |
3470 |
3804 |
3581 |
1076 |
4578 |
2534 |
2022 |
2356 |
| 480-565 |
800 |
SS |
8338 |
3867 |
4080 |
4724 |
1327 |
3429 |
2946 |
2419 |
2632 |
| 480-565 |
800 |
SL & LL |
10630 |
3867 |
4080 |
4724 |
1327 |
4578 |
2946 |
2419 |
2632 |
| 670-780 |
800 |
SS |
8338 |
3912 |
4235 |
3581 |
1327 |
3429 |
2915 |
2540 |
2788 |
| 670-780 |
800 |
SL & LL |
10630 |
3912 |
4235 |
4724 |
1327 |
4578 |
2915 |
2540 |
2788 |
| 670-780 |
1420 |
ML & LL |
10754 |
4413 |
4594 |
4724 |
1499 |
4578 |
3077 |
3042 |
3756 |
| 920-1067 |
1420 |
ML & LL |
10754 |
4413 |
4594 |
4724 |
1499 |
4578 |
3077 |
3042 |
3756 |
| 920-1067 |
2100 |
LL |
10801 |
4667 |
4750 |
4724 |
1499 |
4578 |
3375 |
3296 |
3302 |
CL1 CAN BE AT EITHER END OF MACHINE AND IS
REQUIRED FOR TUBE PULL CLEARANCE.
CL2 IS ALWAYS AT THE OPPOSITE END OF MACHINE FROM CL1 AND IS
REQUIRED FOR SERVICE CLEARANCE.
| CENTRAVAC WATER CONNECTION PIPE
SIZE |
| Water |
Shell Size |
| Passes |
032 |
050 |
080 |
142 |
210 |
| EVAPORATOR |
Metric Pipe Size (Millimeters) |
| 1 PASS |
DN200 |
DN250 |
DN300 |
DN400 |
DN400 |
| 2 PASS |
DN150 |
DN200 |
DN250 |
DN300 |
DN350 |
| 3 PASS |
DN125 |
DN150 |
DN200 |
DN250 |
DN300 |
| CONDENSER 2 PASS |
DN150 |
DN200 |
DN250 |
DN300 |
DN350 |
|
Copyright © 19962009 AECinfo.com
|
|