| Controls Unit Control Panel Sequence of Operation
Conventional "relay logic"
circuits have, been replaced by software imbedded in the CenTraVac ® microprocessor
controller. The functions of the microprocessor are
divided into six standard modules. Optional modules are available for those
applications that require additional control
capability. Optional communication interface modules
are available for alternative control sources. All modules communicate with
each other on the interprocessor communication bus
(IPC).
All information is available and all
setpoint/setup adjustments can be accomplished at the operator interface. An
optional remote display permits the operator to monitor
and operate the chiller from a remote location.
The six standard modules consist of a
chiller module, a circuit module, a starter module, a stepper module, a purge
module and local display module.
The chiller module
is the master of the chiller. It communicates commands
to other modules and collects data/status/ diagnostic information from other modules
over the IPC.
The chiller module performs the leaving evaporator fluid temperature and limit control
algorithms arbitrating capacity against any operating
limit the chiller may find itself working against.
The circuit module is assigned inputs and outputs associated with the refrigerant
and lubrication circuits.
The starter module
provides control of the starter when starting, running
and stopping the motor. It provides interface to and control of wye-delta, across the line, primary reactor, auto transformer,
solid-state starters and Trane Adaptive Frequency
drive. The starter module also provides
protection to both the motor and the compressor in the form of running overload, phase reversal, phase loss, phase unbalance, momentary
power loss and compressor surge. All diagnostics are
communicated across the IPC to the human interface.
The stepper module
is designed to drive the stepper motor inlet guide
vane actuator and other flow control devices within a system. This module receives
from the chiller module the direction and distance to
drive the inlet guide vanes and then generates the
appropriate signals to operate the stepper motor.
The purge module
provides control of the purge including all the inputs
and outputs to control the purge, to optimize both purge and chiller efficiency,
and to communicate purge diagnostics to the human
interface.
Before anything can begin, 115 volt
(50 or 60 Hz) power is applied to the control panel. In that several control source devices may coexist, the operator
determines which device has priority via the operator
interface. All control settings at that control source
are then in effect (i.e. active setpoints).
A control source is the device
that determines setpoints and whether the chiller is auto/off (such as local control panel, remote control display, 4-20 ma external
device, Tracer ® , generic BAS).
For this sequence of operation it
will be assumed that the control source has signaled the chiller to be in Automatic (i.e. when there is a load present, the chiller
will turn on and when the load disappears, the chiller
will turn off). It is also assumed that no diagnostic
has occurred either prior to start-up or during run time and that no "special" applications exist.
| Power Off |
|
| Power On |
|
| Auto |
"Automatically
Ready to Start |
| Evaporator Pump On |
Waiting for Need to Cool" |
| In Parallel: Restart Inhibit |
"Restart Temporarily
Prevented |
| Prelubrication |
- Time Remaining [ : ]" |
| Condenser Flow Established |
"Establishing Condenser Flow
|
| Start |
and Oil Pressure" |
| Run: Normal |
"Starting
Compressor" |
|
"Running Normal" or |
| Softloading |
"Softloading" or |
| Evaporator Limit |
"Running - Capacity
Limited by |
| Condenser Limit |
Low Evaporator
Temperature" or |
| Current/Demand Limit |
"Running - Capacity
Limited by |
| Unload |
High Condenser Pressure" |
|
"Machine is Preparing to
Shutdown" |
| Stop |
"Operator Initiated Stop |
| In Parallel:Close Inlet Guide
Vanes |
Press Auto to Restart" |
Run Compressor
|
"Post Lubricating - |
Post Lube
|
Time Remaining [ : ] |
| Auto |
"Automatically Read
to Start - |
|
Waiting
for Need to Cool" |
|