Homepage  
Search
find:
search for:
   
 
Site Navigation
News / Publications
Jobs
Service
   Add this page to Google Bookmarks
   Add this page to Mister Wong
   Add this page to del.icio.us
 
   Trane Company (The)  20 - 80 Ton Self Contained Air Conditioners  

20-80 Ton Self-Contained Air Conditioners - Page 13

 

 

Unit Control Features (cont.)

They are:

  • Supply air fan off due to running current overload, short circuit, or loss of duct static pressure, or high duct pressure.
  • Input voltage phase reversal, or phase loss.
  • Unit control module failure.
  • Sensor failure; supply air temperature out of range (low temp.).
  • Entering air high temperature (o p t i o n a l ).

The following malfunctions require manual reset to re-enable the affected compressor circuit and clear the diagnostic code:

  • Compressor(s) off due to running current overload or short circuit.
  • Compressor(s) off via high or low pressure cutouts.
  • Compressor(s) off due to high motor or high refrigerant discharge temperature, or low evaporator suction temperature.

The above are the only diagnostics that require manual reset. All other diagnostic code conditions do not normally result in unit or circuit shut down and the diagnostic resets automatically when the condition is corrected.

Supply Fan

The supply fan is off in the Stop/Reset mode. The fan is on continuously when the Fan On Ventilate function is used and in either Auto switch night heat morning warmup position except on units with the Programmable Night Heat Morning Warmup and Time Clock control options. Refer to page 15 for a description of these options.

Step Control

The steps of mechanical cooling are controlled based on supply air temperature on VAV units and on zone temperature on constant volume units. Refer to the data section, pages 28 through 83 for number of capacity control steps for each unit.

The control system logic will permit compressor operation only after supply fan operation is called for. Compressor operation will not be permitted if the supply fan is off. Also, compressor operation will not be permitted when condenser entering water temperature is below 55 degrees F on units without condensing pressure control, and below 35 degrees F on units with condensing pressure control valve.

Remote Supply Air Setpoint Adjustment (Optional)

On VAV units, the supply air setpoint can be set or adjusted remotely. The unit contains a pair of terminals that will accept a 4-20 milliamp or 0-10 volt electronic signal. This signal can be provided by a Tracer system or other building automation systems.

Alarm Contact Closure

The alarm contact closure output is energized in the event of any malfunction that normally initiates a diagnostic code display. Refer to Figure 13-1 for a list of the diagnostics that will cause a code to be displayed. Also, the following additional diagnostics are included:

  • Operation of the entering air temperature sensor
  • Loss of condenser water flow; if flow switch is present

Setpoints

COOLING — The cooling setpoint is adjustable from 50 to 90 degrees F. On VAV units the setpoint is adjusted at the unit control module. On constant volume units the setpoint is adjusted at the unit control module, or, can be remotely adjusted with the addition of an optional remote potentiometer.

HEATING — The heating setpoint is adjustable from 40 to 90 degrees F. On both VAV and constant volume units, the setpoint is adjustable only at the unit control module.

Fan On/Ventilate

A pair of field accessible terminals is provided which can energize ventilation functions. When the connection between them is closed, the fan will start, the airside economizer fresh air damper (if provided) will be driven full open, and the ventilate output will be energized. The inlet guide vanes will be active.

This input will override the external interlock auto/stop input. It will also override Tracer computer inputs when energizing the ventilation functions. However, both the Tracer computer input and the Fan On\ Ventilate input must be "off" to terminate the Fan On\ Ventilate mode.

During the Fan On\ Ventilate mode all cooling and heating functions will be locked out. Manual reset is not required to restore normal operation.

This input will be overridden by the Unit Switch when it is in the Stop/Reset position.

External Interlock Auto/Stop

A pair of field accessible terminals is provided which will cause shutdown of the unit when the connection between them is open. Unit operation will be restored when the connection is remade. The shutdown is similar to placing the Unit Switch in the Stop/Reset position. This feature will override any Tracer® computer inputs. Manual reset is not required to restore operation.

Any malfunction that requires manual reset is not affected by this input. Manual reset is still required

Setpoint Reset (Optional)

On VAV units, supply air temperature setpoint can be reset upward as the space temperature drops below a preset point called the reset reference setpoint. This setpoint can be set in a range from 60 to 80 degrees F. The amount that the supply air temperature is reset upward is based on a setting called the reset gain. This setting can be adjusted to allow the supply air temperature to be reset upward from 1 degree F for every 1 degree drop below the reset reference setpoint to 8 degrees F for every 1 degree drop below the reset reference setpoint.

A reset limit adjustment is also provided to limit the maximum supply air setpoint. This limit can be set in a range from 65 to 90 degrees F.

A zone temperature sensor to sense when the space temperature falls below the reset reference setpoint is shipped with the unit for field installation in the remote space.

Frost Protection Control Due to the unique design of the unit control module and the 3-D™ Scroll compressor, frost protection is provided without the use of inefficient hot gas bypass. Frosting is controlled by measuring suction temperature on each circuit. If the suction temperature falls below 28 degrees for the required time, that circuit is turned off and another circuit is brought on line to handle the load. The first circuit remains off until the temperature rises above 34 degrees for the required time, and can then be brought back on line as required.

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2009 AECinfo.com