System Control Options (contd.)   

control module digital readout (refer to Figure 13-1) are accessible at the Tracer CRT. In addition, there are several more points of information available through the Tracer computer. Included are:

  • Compressor on/off status
  • Ventilation status
  • Condenser water flow status
  • % FLA supply fan
  • Heat status
  • Heat hours and starts
  • Each compressor operating hours
  • Each compressor starts
  • Supply fan operating hours
  • Supply fan starts
  • % RLA of each compressor
  • Supply air pressure
  • Supply air temperature
  • Suction temperature of each circuit
  • Entering economizer water temperature
  • Zone temperature
  • Entering condenser water temperature
  • Leaving condenser water temperature
  • Supply air temperature reset signal
  • Morning warmup sensor temperature
  • Entering air temperature

Time Clock

With this option, a programmable timer is supplied and wired to the External Interlock Auto/Stop input to provide on/off control of the unit. The timer is factory mounted and is accessible without opening any unit panels. The timer is a seven day timer with a minimum of 4 operations per day (two on and two off). The timer has a permanent built-in rechargeable battery back-up system.

Unit Control Module The unit control module is programmed at the factory to provide complete control of unit operation in all standard and optional operating modes. This control logic is an integral part of the unit microprocessor and cannot be modified. The following table (17-1 ) illustrates the status of the control outputs during each of the unit operating modes.

Table (17-1 ) Control Output Status

   

When available

Operating Modes
Unoccupied Night Heat Morning Warm-up Occupied Heating Occupied Cooling Timed Override Stop Fan On Ventilate Freeze Protect
Supply Fan Standard Enabled On On On On Off On Off
Mechanical Cooling Standard Disabled Disabled Disabled Enabled Enabled Disabled Disabled Disabled
Waterside Economizer Optional Disabled Disabled Disabled Enabled Enabled Disabled Disabled Full Flow
Airside Economizer Optional Disabled Disabled Set to inimum Position Enabled Enabled Closed Full Open Closed
Inlet Guide Vanes Optional Enabled Enabled Enabled Enabled Enabled Closed Enabled Closed
Unoccupied Output NHMW and / or ICS Energized Energized De-energized De-energized De-energized De-energized De-energized Energized
Ventilation Output NHMW and / or ICS De-energized De-energized Energized Energized Energized De-energized Energized De-energized
Heat / Cool Output NHMW and / or ICS Energized Energized Energized De-energized De-energized De-energized De-energized De-energized
Heat Relay Output NHMW and / or ICS Enabled Enabled Energized De-energized De-energized De-energized De-energized De-energized
Condenser Waterloop Interlock Output NHMW and / or ICS De-energized De-energized De-energized Energized Energized De-energized De-energized Energized

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2009 AECinfo.com