Homepage  
Search
find:
search for:
   
 
Site Navigation
News / Publications
Jobs
Service
   Add this page to Google Bookmarks
   Add this page to Mister Wong
   Add this page to del.icio.us
 
   Trane Company (The)  20 - 80 Ton Self Contained Air Conditioners  

20-80 Ton Self-Contained Air Conditioners - Page 17

 

 

Options (cont.)

Flexible Horizontal Discharge

The design of this option reduces discharge sound power level from typical ducted systems which results in quieter system operation. The option is factory mounted on the top of the unit and has been engineered to optimize unit discharge performance by eliminating duct turns or complex transitions. In addition to improving the system sound levels, this also reduces system installed cost.

Openings for attaching ductwork can be factory cut to customer requirements helping to further reduce the system installed cost.

These discharge openings can be positioned for single or multiple discharge from the front, rear, or either side. This allows designers to position the unit within the equipment room to minimize floor space requirements while maximizing system performance. Refer to page 9 for more details on installation advantages.

Inlet Guide Vanes

Inlet guide vanes are among the most efficient and cost effective means of providing airflow modulation in VAV systems. Trane patented inlet guide vanes have proven reliability with thousands of installations in Self-Contained units, Climate Changer® air handlers, and VAV Rooftop units.

The inlet guide vanes are factory instaIled complete with electric actuator, linkage, and static pressure controller. The duct pressure sensing probe is shipped loose for field installation. Field supplied 1/4 inch O.D. plastic tubing is to be installed between the probe and the unit mounted static pressure controller.

The inlet guide vanes are controlled by the supply air static pressure controller, which is part of the unit control module. The inlet vanes will move to the closed position upon supply fan shutdown if unit power is on. Inlet vanes will be in the closed position whenever the fan starts and will then modulate in response to supply air static pressure. T

The static pressure controller offers field adjustment of the setpoint and control band by means of an adjustment knob on the control panel.

Waterside Economizer

There are a number of alternatives available with this option:

  • 4 Row — mechanically cleanable
  • 4 Row — chemically cleanable
  • 2 Row — mechanically cleanable

Each economizer is available with two control selections:

  • Modulating Standard Control
  • Modulating Energy Saving Control

All economizer control valves, piping between the economizer and the condenser, and all wiring are factory installed. All piping and control valves are located within the unit enclosure, and all water connections and controls are located on the left side of the unit. Service access for cleaning is provided by removing panels on the left side of the unit.

The waterside economizer will take advantage of cooling tower water to either precool the entering air to aid the mechanical cooling process or, if the water temperature is low enough, provide total system cooling.

MODULATING STANDARD CONTROL — For economizer control, whenever the entering water temperature is at least 5 degrees F below the return air temperature, the economizer function is enabled and water is routed through the economizer first, and then through the condenser. The economizer acts as the first stage of cooling. If the economizer is unable to maintain the supply air setpoint, the unit control module will bring on compressors as required to meet the setpoint.

When the economizer is acting as the first stage of cooling, and no compressor is in operation, water flow is modulated through the economizer in response to supply air temperature on VAV units and in response to zone temperature on constant volume units. Since the economizer valve and the bypass valve are proportional, full water flow through the unit is always maintained. If the entering water temperature is not at least 5 degrees F below the return air temperature, the economizer function is disabled, the economizer valve closes and water is routed through the condenser only.

Waterside economizer flow is controlled by two valves; one on the inlet to the economizer and one which bypasses water around the economizer. Whenever the supply fan is off, the bypass water valve is fully open and the economizer valve is fully closed. Whenever the unit is started, the valves are initially in this position until the unit control module enables the economizer function.

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2009 AECinfo.com