Notes:
1. Compressors are Trane 3D scroll.
2. EER based on 80/67 degrees F to the evaporator
coil, nominal airflow, and 85-95 degree condenser water.
3. All units operate with R-22. Unit ships with full
operating charge.
4. Shipping weights will exceed weights in table by
approximately 150 lbs.
5. Unit weights include inlet guide vanes and
controls, full refrigerant charge, and valves on units with waterside economizer.
6. SWUD 20 does not have enhanced capacity
refrigerant tubes.
Notes:
RLA - Rated load amps
Compressor LRA - Locked rotor amps
Fan Motor LRA - Locked rotor amps, N.E.C. Table 430 -
151
FLA - Full load amps, N.E.C. Table 430 - 150
Compressor KW - Based on 80/70 degrees F to evaporator
coil, nominal airflow, and 105 degrees F condensing temperature, 3 phase, 60 Hertz
Fan Motor KW - Based on rated motor horsepower, 3
phase, 60 Hertz Voltage utilization range is + 10 percent
Determination of minimum circuit ampacity (MCA).
MCA 1.25 x largest motor amps (FLA or RLA) + the sum of
the remaining motor amps.
Determination of maximum fuse size (MFS) and maximum
circuit breaker size (MCB). When compressor is largest load:
MFS and MCB = 2.25 x largest compressor RLA + the sum
of the remaining compressor RLA!s + supply fan (FLA).
When supply fan is largest load:
MFS and MCB = 4.0 x supply fan FLA + the sum of the
remaining compressor RLxs.