Homepage  
Search
find:
search for:
   
 
Site Navigation
News / Publications
Jobs
Service
   Add this page to Google Bookmarks
   Add this page to Mister Wong
   Add this page to del.icio.us
 
   Trane Company (The)  20 - 80 Ton Self Contained Air Conditioners  

20-80 Ton Self-Contained Air Conditioners - Page 29

 

 

SWUD 20 Waterside Economiser Capacity

TABLE 30-1 -Gross Cooling Capacity

2 Row Economizer 8000 CFM
Entering Water Temperature F
      45 55 65 75
Ent  DB Ent WB GPM Tot MBH Sen  MBH LWT Tot MBH Sen MBH LWT Tot MBH Sen MBH LWT Tot MBH Sen MBH LWT
    41 125 106 51 70 70 58 24 24 66      
  62 50 134 110 50 74 74 58 25 25 66      
    60 142 113 50 77 77 58 26 26 66      
70   70 148 116 49 78 78 57 27 27 66      
    41 163 78 53 92 53 59 24 24 66      
  67 50 178 83 52 100 55 59 25 25 66      
    60 190 88 51 106 58 59 26 26 66      
    70 200 91 51 113 60 58 27 27 66      
    41 139 139 52 94 94 60 48 48 67      
  62 50 147 147 51 98 98 59 50 50 67      
    60 153 153 50 102 102 58 52 52 67      
    70 159 158 50 105 105 58 53 53 67      
    41 163 116 53 98 93 60 48 48 67      
75 67 50 177 121 52 104 95 59 50 50 67      
    60 189 125 51 111 97 59 52 52 67      
    70 199 129 51 115 98 58 53 53 67      
    41 207 86 55 135 63 62 58 39 68      
  72 50 226 92 54 147 67 61 62 41 67      
    60 242 98 53 157 70 60 67 42 67      
    70 254 102 52 166 72 60 70 43 67      
    41 162 162 53 118 118 61 72 72 68 24 24 76
  62 50 170 170 52 123 123 60 75 75 68 25 25 76
    60 177 177 51 127 127 59 77 77 68 26 26 76
    70 181 181 50 131 131 59 79 79 67 27 27 76
    41 171 156 53 118 118 61 72 72 68 24 24 76
80 67 50 183 161 52 123 123 60 75 75 68 25 25 76
    60 193 165 51 128 128 59 77 77 68 26 26 76
    70 201 16B 51 131 131 59 79 79 67 27 27 76
    41 206 124 55 136 101 62 72 72 69 24 24 76
  72 50 225 130 54 147 105 61 76 75 68 25 25 76
    60 241 136 53 157 108 60 78 78 68 26 26 76
    70 254 140 52 165 110 60 80 80 67 27 27 76
    41 185 185 54 141 141 62 95 95 70 49 49 77
  62 50 195 195 53 148 148 61 100 100 69 50 50 77
    60 202 202 52 153 153 60 103 103 68 52 52 77
    70 207 207 51 157 157 59 105 105 68 53 53 77
    41 187 197 54 142 142 62 96 96 70 49 49 77
85 67 50 197 197 53 148 148 61 100 100 69 51 51 77
    60 205 205 52 153 153 60 103 103 68 52 52 77
    70 213 210 51 157 157 59 106 106 68 53 53 77
    41 210 163 55 147 143 62 96 96 70 49 49 77
  72 50 227 169 54 156 145 61 100 100 69 51 51 77
    60 242 174 53 163 148 60 103 103 68 52 52 77
    70 253 178 52 171 150 60 106 106 68 53 53 77

NOTE: Each curve provides total water pressure drop tnrough the entire unit including all accessories and internal valves and piping. Do not add curves together.

TABLE 30-2-Gross Cooling Capacity

4 Row Economizer 8000 CFM
Entering Water Temperature F
      45 55 65 75
Ent  DB Ent WB GPM Tot MBH Sen  MBH LWT Tot MBH Sen MBH LWT Tot MBH Sen MBH LWT Tot MBH Sen MBH LWT
    41 167 128 53 88 88 59 30 30 66      
  62 50 178 132 52 92 91 59 31 31 66      
    60 188 136 51 94 94 58 31 31 66      
70   70 197 140 51 96 96 58 32 32 66      
    41 220 100 56 124 65 61 30 30 66      
  67 50 239 107 55 134 69 60 31 31 66      
    60 254 113 53 143 72 60 32 32 66      
    70 266 118 53 150 74 59 32 32 66      
    41 180 173 54 117 117 61 59 59 68      
  62 50 190 186 53 122 122 60 61 61 67      
    60 198 189 52 125 125 59 63 63 67      
    70 204 191 51 127 127 59 64 64 67      
    41 221 141 56 129 108 61 59 59 68      
75 67 50 238 148 55 139 111 61 61 61 67      
    60 253 154 53 146 114 60 63 63 67      
    70 265 158 53 152 116 59 64 64 67      
    41 281 113 59 181 79 64 78 47 69      
  72 50 304 121 57 199 84 63 84 49 68      
    60 324 129 56 211 89 62 90 51 68      
    70 340 134 55 222 92 61 94 52 68      
    41 203 203 55 147 147 62 89 89 69 30 30 76
  62 50 211 211 53 152 152 61 92 92 69 31 31 76
    60 218 218 52 156 156 60 94 94 68 32 32 76
    70 222 222 51 159 159 60 96 96 68 32 32 76
    41 227 184 56 148 148 62 89 89 69 30 30 76
80 67 50 242 190 55 155 155 61 92 92 69 31 31 76
    60 255 195 53 160 160 60 95 95 68 32 32 76
    70 266 199 53 165 161 60 96 96 68 32 32 76
    41 280 153 59 184 121 64 91 91 69 30 30 76
  72 50 304 162 57 198 125 63 96 93 69 31 31 76
    60 323 169 56 211 130 62 99 95 68 32 32 76
    70 339 175 55 220 133 61 103 95 68 32 32 76
    41 232 232 56 176 176 64 118 118 71 60 60 78
  62 50 241 241 55 182 182 62 122 122 70 62 62 77
    60 248 248 53 187 187 61 126 126 69 63 63 77
    70 253 253 52 191 191 60 128 128 69 64 64 77
    41 242 242 57 176 176 64 119 119 71 60 60 78
85 67 50 255 247 55 183 183 62 123 123 70 62 62 77
    60 266 251 54 188 188 61 126 126 69 63 63 77
    70 275 255 53 191 191 60 128 128 69 64 64 77
    41 283 195 59 193 165 64 119 119 71 60 60 78
  72 50 305 203 57 206 169 63 123 123 70 62 62 77
    60 323 210 56 217 172 62 126 126 69 63 63 77
    70 338 215 55 225 175 61 129 129 69 65 65 77

NOTES:

1 .Dotted line on construction filters indicates CFM where face velocity exceeds manufacturer's recommended maximum of 300 FPM. After startup, construction filters must be replaced with medium velocity or high velocity filters.

2. Air pressure drop through electric heat is .05 inches WC.

3. Refer to Page 27 for pressure drop through flexible horizontal discharge.