SWUD 25 Waterside Economiser Capacity

TABLE 38-1 -Gross Cooling Capacity

2 Row Economizer 10000 CFM
Entering Water Temperature F
      45 55 65 75
Ent  DB Ent WB GPM Tot MBH Sen  MBH LWT Tot MBH Sen MBH LWT Tot MBH Sen MBH LWT Tot MBH Sen MBH LWT
    50 144 126 51 82 82 58 28 28 66      
  62 63 156 131 50 86 86 58 29 29 66      
    75 164 134 49 89 89 57 30 30 66      
70   80 166 135 49 90 90 57 30 30 66      
    50 188 91 53 106 62 59 28 28 66      
  67 63 206 97 52 115 65 59 29 29 66      
    75 218 102 51 122 68 58 30 30 66      
    80 223 103 51 125 68 58 30 30 66      
    50 162 162 51 110 110 59 55 55 67      
  62 63 171 171 50 115 115 59 59 59 67      
    75 178 178 50 119 119 58 60 60 67      
    80 180 180 49 120 120 58 61 61 67      
    50 188 136 53 113 110 60 56 56 67      
75 67 63 206 143 52 120 113 59 59 59 67      
    75 218 147 51 125 115 58 60 60 67      
    80 222 149 51 129 116 58 61 61 67      
    50 239 100 55 155 73 61 66 46 68      
  72 63 262 108 53 170 78 60 72 48 67      
    75 278 113 52 180 81 60 76 49 67      
    80 283 115 52 184 82 60 78 50 67      
    50 188 188 53 137 137 60 83 83 68 28 28 76
  62 63 199 199 51 144 144 60 87 87 68 29 29 76
    75 206 206 50 149 149 59 90 90 67 30 30 76
    80 208 208 50 150 150 59 91 91 67 31 31 76
    50 198 186 53 137 137 60 83 83 68 28 28 76
80 67 63 212 191 52 144 144 60 87 87 68 29 29 76
    75 222 195 51 149 149 59 90 90 67 30 30 76
    80 226 196 51 150 150 59 91 91 67 31 31 76
    50 238 146 55 157 120 61 84 84 68 28 28 76
  72 63 261 154 53 170 124 60 88 88 68 30 30 76
    75 277 159 52 180 127 60 91 91 67 30 30 76
    80 283 161 52 184 128 60 92 92 67 31 31 76
    50 216 216 54 165 165 62 111 111 69 57 57 77
  62 63 228 228 52 173 173 60 116 116 69 59 59 77
    75 235 235 51 178 178 60 120 120 68 61 61 77
    80 238 238 51 180 180 60 121 121 68 61 61 77
    50 218 217 54 165 165 62 111 111 69 57 57 77
85 67 63 230 230 52 173 173 61 117 117 69 59 59 77
    75 238 238 51 179 179 60 120 120 68 61 61 77
    80 241 241 51 181 181 60 121 121 68 61 61 77
    50 242 193 55 170 170 62 111 111 69 57 57 77
  72 63 263 200 53 180 173 61 117 117 69 59 59 77
    75 277 205 52 188 176 60 120 120 68 61 61 77
    80 283 207 52 190 177 60 122 122 68 62 62 77

NOTE: Each curve provides total water pressure drop tnrough the entire unit including all accessories and internal
valves and piping. Do not add curves together.

TABLE 38-2-Gross Cooling Capacity

4 Row Economizer 10000 CFM
Entering Water Temperature F
      45 55 65 75
Ent  DB Ent WB GPM Tot MBH Sen  MBH LWT Tot MBH Sen MBH LWT Tot MBH Sen MBH LWT Tot MBH Sen MBH LWT
    50 194 152 53 104 104 59 35 35 66      
  62 63 209 158 52 108 108 58 37 37 66      
    75 219 162 51 111 111 58 37 37 66      
70   80 224 164 51 112 112 58 37 37 66      
    50 257 118 55 144 77 61 35 35 66      
  67 63 279 126 54 157 82 60 36 36 66      
    75 295 132 53 165 85 59 37 37 66      
    80 300 134 53 169 86 59 38 38 66      
    50 211 208 53 138 138 61 70 70 68      
  62 63 223 213 52 144 144 60 73 73 67      
    75 231 230 51 148 148 59 74 74 67      
    80 234 231 51 149 149 59 75 75 67      
    50 257 167 55 150 129 61 70 70 68      
75 67 63 279 176 54 162 133 60 73 73 67      
    75 294 182 53 169 136 60 74 74 67      
    80 300 184 52 172 137 59 75 75 67      
    50 326 132 58 211 93 63 90 56 69      
  72 63 356 142 56 231 100 62 98 58 68      
    75 377 150 55 245 104 62 104 60 68      
    80 384 152 55 250 106 61 106 61 68      
    50 240 240 55 173 173 62 104 104 69 35 35 76
  62 63 250 250 53 180 180 61 109 109 68 37 37 76
    75 257 257 52 184 184 60 111 111 68 37 37 76
    80 259 259 51 186 186 60 112 112 68 38 38 76
    50 265 220 56 175 174 62 105 105 69 35 35 76
80 67 63 283 228 54 182 182 61 109 109 68 37 37 76
    75 296 233 53 188 188 60 112 112 68 37 37 76
    80 302 235 53 190 190 60 113 113 68 38 38 76
    50 325 181 58 213 144 64 107 107 69 35 35 76
  72 63 355 192 56 230 150 62 112 112 69 37 37 76
    75 374 199 55 244 154 62 116 114 68 37 37 76
    80 381 202 55 249 155 61 117 114 68 38 38 76
    50 274 274 56 207 207 63 139 139 71 70 70 78
  62 63 286 286 54 216 216 62 145 145 70 73 73 77
    75 293 293 53 221 221 61 148 148 69 75 75 77
    80 296 296 52 223 223 61 149 149 69 75 75 77
    50 283 277 56 208 208 63 140 140 71 70 70 78
85 67 63 299 299 55 216 216 62 145 145 70 73 73 77
    75 311 306 53 222 222 61 149 149 69 75 75 77
    80 314 307 53 224 224 61 150 150 69 75 75 77
    50 329 233 58 224 198 64 140 140 71 71 71 78
  72 63 356 242 56 240 203 63 146 146 70 73 73 77
    75 375 249 55 251 206 62 149 149 69 75 75 77
    80 382 252 55 255 207 61 150 150 69 76 76 77

NOTES:

1 .Dotted line on construction filters indicates CFM where face velocity exceeds manufacturer's recommended
maximum of 300 FPM. After startup, construction filters must be replaced with medium velocity or high velocity filters.

2. Air pressure drop through electric heat is .05 inches WC.

3. Refer to Page 27 for pressure drop through flexible horizontal discharge.