Homepage  
Search
find:
search for:
   
 
Site Navigation
News / Publications
Jobs
Service
   Add this page to Google Bookmarks
   Add this page to Mister Wong
   Add this page to del.icio.us
 
   Trane Company (The)  Series R Rotary Liquid Chillers  

Series R Rotary Liquid Chillers - Page 218

 

 

Application Considerations

 

Figure A-1 -- Recommended   Piping Components For Typical  Evaporator Installation

Typical Water Piping

All building water piping must be flushed prior to making final connections to the chiller. To reduce heat loss and prevent condensation, insulation should be installed. Expansion tanks are also usually required so that chilled water volume changes can be accommodated. A typical piping arrangement is shown in Figure A-1.

Short Water Loops

The proper location of the temperature control sensor is in the supply (outlet) water. This location allows the building to act as a buffer and assures a slowly changing return water temperature. If there is not a sufficient volume of water in the system to provide an adequate buffer, temperature control can be lost, resulting in erratic system operation and excessive compressor cycling. A short water loop (less than two gallons/nominal ton) has the same effect as attempting to control from the building return water.

To prevent the effect of a short water loop, the following items should be given careful consideration:

A storage tank or larger header pipe to increase the volume of water in the system and, therefore, reduce the rate of change of the return water temperature.

Multiple Unit Operation

Whenever two or more units are used on one chilled water loop, Trane recommends that their operation be controlled from a single control device, such as a Trane Tracer® system.

1

Series Operation

Some systems require large chilled water temperature drops (16 to 24 F). For those installations, two units with their evaporators in series are usually required. Control of the units should be from a common temperature controller to prevent the separate thermostats fighting one another and continually hunting. It is possible to control from the two individual unit controls, but a common temperature controller provides a positive method for preventing control overlap, more closely matches system load, and simplifies compressor lead-lag capability.

2

Parallel Operation

Some systems require more capacity or standby capability than a single machine can provide. For those installations, two units with their evaporators in a parallel configuration are typical. The only effective way of controlling two units in parallel is with a single temperature controller. Two individual temperature controllers are not capable of   providing reliable system  control and will often result in unsatisfactory operation and possible compressor failure.

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2009 AECinfo.com