   Trane Company (The)  Series R Rotary Liquid Chillers  

Series R Rotary Liquid Chillers - Page 229

 

 

Performance Data

Table P-9 - RTAA 155 Performance Data

English

Entering Condenser Air temperature (Degrees F)
LWT (Deg F)   75     85     95     105     115  
  Tons KW EER Tons KW EER Tons KW EER Tons KW EER Tons KW EER
40 155.0 140.3 12.0 147.2 155.2 10.4 139.0 172.0 8.9 130.5 190.9 7.6 121.5 211.9 6.5
42 160.7 142.7 12.2 152.7 157.6 10.6 144.2 174.6 9.1 135.3 193.5 7.8 126.0 214.6 6.6
44 166.5 145.2 12.5 158.3 160.2 10.9 149.5 177.2 9.4 140.3 196.2 8.0 130.6 217.3 6.8
45 169.5 146.4 12.6 161.1 161.5 11.0 152.1 178.5 9.5 142.7 197.5 8.1 132.9 218.7 6.8
46 172.5 147.7 12.7 163.9 162.8 11.1 154.8 179.9 9.6 145.3 199.0 8.2 133.0 215.4 7.0
48 178.5 150.2 13.0 169.7 165.4 11.3 160.3 182.6 9.8 150.4 201.8 8.3 134.0 210.7 7.2
50 184.6 152.8 13.2 175.5 168.1 11.5 165.8 185.4 9.9 155.6 204.7 8.5 134.9 205.9 7.4
55 200.4 159.6 13.8 190.6 175.2 12.0 180.1 192.8 10.4 168.9 212.4 8.9 138.4 196.9 7.9

Notes :

1. Ratings based on sea level altitude and evaporator fouling factor of 0.00025

2. Consult Trane representative for performance at temperature outside of the ranges shown.

3. kW input is for compressors only.

4. EER = Energy Efficient Ratio (Btu/watt-hour). Power inputs include compressors, condenser fans and control power.

5. Ratings are based on an evaporator temperature drop of 10 F.

6. 115 F Performance data reflect Adaptive Control Microprocessor control algorithms.

7. Interpolation is permitted, extrapolation is not.

8. Rated in accordance with ARI Standard 590-92.

Metric

Entering Condenser Air temperature (Degrees C)

LWT (Deg C) 30 35 40 45
kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
6 541.7 160.3 3.1 514.5 175.6 2.7 485.9 192.7 2.3 456.1 211.5 2.0
8 577.1 165.0 3.2 548.1 180.4 2.8 517.8 197.6 2.4 477.6 211.5 2.1
10 613.6 169.9 3.3 582.9 185.4 2.9 550.7 202.8 2.5 488.9 205.6 2.2

Notes :

1. Evaporator fouling factor is 0.00025 per ARI Standard 550-92

2. Interpolation between points is permissible. Extrapolation is not permitted.

3. kWi input is for the compressors only.

4. COP = Coefficient of Performance (kWo/kWi).Power includes compressors, condenser fans and control power.

5. Rated in accordance with ARI Standard 590-92.

6. Ratings are based on an evaporator temperature drop of 5.6 C.

Table P- 10 - RTAA 170 Performance Data

English

Entering Condenser Air temperature (Degrees F)
LWT (Deg F)   75     85     95     105     115  
  Tons KW EER Tons KW EER Tons KW EER Tons KW EER Tons KW EER
40 171.1 159.3 11.7 162.5 175.0 10.2 153.6 193.1 8.8 144.6 213.5 7.6 130.7 226.8 6.5
42 177.0 162.2 11.9 168.1 178.0 10.4 159.0 196.1 9.0 149.7 216.7 7.7 133.5 226.2 6.6
44 183.0 165.2 12.1 173.8 181.0 10.6 164.5 199.3 9.2 154.9 220.0 7.9 136.2 225.5 6.8
45 186.1 166.7 12.2 176.7 182.6 10.7 167.2 200.9 9.3 157.5 221.6 8.0 137.0 223.8 6.9
46 189.1 168.2 12.3 179.7 184.1 10.8 170.0 202.5 9.3 160.1 223.3 8.0 137.9 222.1 7.0
48 195.3 171.3 12.5 185.6 187.4 11.0 175.6 205.8 9.5 165.4 226.7 8.2 138.6 216.8 7.2
50 201.7 174.4 12.7 191.6 190.6 11.1 181.4 209.2 9.7 170.9 230.2 8.3 140.2 213.4 7.4
55 217.9 182.6 13.1 207.1 199.1 11.6 196.1 218.0 10.1 184.8 239.4 8.7 143.1 202.2 7.9

Notes :

1. Ratings based on sea level altitude and evaporator fouling factor of 0.00025

2. Consult Trane representative for performance at temperature outside of the ranges shown.

3. kW input is for compressors only.

4. EER = Energy Efficient Ratio (Btu/watt-hour). Power inputs include compressors, condenser fans and control power.

5. Ratings are based on an evaporator temperature drop of 10 F.

6. 115 F Performance data reflect Adaptive Control Microprocessor control algorithms.

7. Interpolation is permitted, extrapolation is not.

8. Rated in accordance with ARI Standard 590-92.

Metric

Entering Condenser Air temperature (Degrees C)

LWT (Deg C) 30 35 40 45
kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
6 595.8 181.0 3.0 566.8 197.4 2.7 537.0 216.0 2.3 485.3 224.3 2.0
8 632.5 186.6 3.1 601.7 203.2 2.7 570.1 221.9 2.4 501.6 221.6 2.1
10 670.1 192.4 3.2 637.8 209.2 2.8 604.6 228.1 2.5 514.5 216.8 2.2

Notes :

1. Evaporator fouling factor is 0.00025 per ARI Standard 550-92

2. Interpolation between points is permissible. Extrapolation is not permitted.

3. kWi input is for the compressors only.

4. COP = Coefficient of Performance (kWo/kWi).Power includes compressors, condenser fans and control power.

5. Rated in accordance with ARI Standard 590-92.

6. Ratings are based on an evaporator temperature drop of 5.6 C.

.

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2009 AECinfo.com