| Performance Data Table P-9 - RTAA 155 Performance Data
English |
| Entering
Condenser Air temperature (Degrees F) |
| LWT (Deg F) |
|
75 |
|
|
85 |
|
|
95 |
|
|
105 |
|
|
115 |
|
| |
Tons |
KW |
EER |
Tons |
KW |
EER |
Tons |
KW |
EER |
Tons |
KW |
EER |
Tons |
KW |
EER |
| 40 |
155.0 |
140.3 |
12.0 |
147.2 |
155.2 |
10.4 |
139.0 |
172.0 |
8.9 |
130.5 |
190.9 |
7.6 |
121.5 |
211.9 |
6.5 |
| 42 |
160.7 |
142.7 |
12.2 |
152.7 |
157.6 |
10.6 |
144.2 |
174.6 |
9.1 |
135.3 |
193.5 |
7.8 |
126.0 |
214.6 |
6.6 |
| 44 |
166.5 |
145.2 |
12.5 |
158.3 |
160.2 |
10.9 |
149.5 |
177.2 |
9.4 |
140.3 |
196.2 |
8.0 |
130.6 |
217.3 |
6.8 |
| 45 |
169.5 |
146.4 |
12.6 |
161.1 |
161.5 |
11.0 |
152.1 |
178.5 |
9.5 |
142.7 |
197.5 |
8.1 |
132.9 |
218.7 |
6.8 |
| 46 |
172.5 |
147.7 |
12.7 |
163.9 |
162.8 |
11.1 |
154.8 |
179.9 |
9.6 |
145.3 |
199.0 |
8.2 |
133.0 |
215.4 |
7.0 |
| 48 |
178.5 |
150.2 |
13.0 |
169.7 |
165.4 |
11.3 |
160.3 |
182.6 |
9.8 |
150.4 |
201.8 |
8.3 |
134.0 |
210.7 |
7.2 |
| 50 |
184.6 |
152.8 |
13.2 |
175.5 |
168.1 |
11.5 |
165.8 |
185.4 |
9.9 |
155.6 |
204.7 |
8.5 |
134.9 |
205.9 |
7.4 |
| 55 |
200.4 |
159.6 |
13.8 |
190.6 |
175.2 |
12.0 |
180.1 |
192.8 |
10.4 |
168.9 |
212.4 |
8.9 |
138.4 |
196.9 |
7.9 |
Notes :
1. Ratings based on sea level altitude and evaporator fouling
factor of 0.00025
2. Consult Trane representative for performance at
temperature outside of the ranges shown.
3. kW input is for compressors only.
4. EER = Energy Efficient Ratio (Btu/watt-hour). Power inputs
include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 10
F.
6. 115 F Performance data reflect Adaptive Control
Microprocessor control algorithms.
7. Interpolation is permitted, extrapolation is not.
8. Rated in accordance with ARI Standard 590-92.
Metric |
Entering
Condenser Air temperature (Degrees C) |
| LWT (Deg C) |
30 |
35 |
40 |
45 |
| kWo |
kWi |
COP |
kWo |
kWi |
COP |
kWo |
kWi |
COP |
kWo |
kWi |
COP |
| 6 |
541.7 |
160.3 |
3.1 |
514.5 |
175.6 |
2.7 |
485.9 |
192.7 |
2.3 |
456.1 |
211.5 |
2.0 |
| 8 |
577.1 |
165.0 |
3.2 |
548.1 |
180.4 |
2.8 |
517.8 |
197.6 |
2.4 |
477.6 |
211.5 |
2.1 |
| 10 |
613.6 |
169.9 |
3.3 |
582.9 |
185.4 |
2.9 |
550.7 |
202.8 |
2.5 |
488.9 |
205.6 |
2.2 |
Notes :
1. Evaporator fouling factor is 0.00025 per ARI Standard
550-92
2. Interpolation between points is permissible. Extrapolation
is not permitted.
3. kWi input is for the compressors only.
4. COP = Coefficient of Performance (kWo/kWi).Power includes
compressors, condenser fans and control power.
5. Rated in accordance with ARI Standard 590-92.
6. Ratings are based on an evaporator temperature drop of 5.6
C.
Table P- 10 - RTAA 170 Performance Data
English |
| Entering
Condenser Air temperature (Degrees F) |
| LWT (Deg F) |
|
75 |
|
|
85 |
|
|
95 |
|
|
105 |
|
|
115 |
|
| |
Tons |
KW |
EER |
Tons |
KW |
EER |
Tons |
KW |
EER |
Tons |
KW |
EER |
Tons |
KW |
EER |
| 40 |
171.1 |
159.3 |
11.7 |
162.5 |
175.0 |
10.2 |
153.6 |
193.1 |
8.8 |
144.6 |
213.5 |
7.6 |
130.7 |
226.8 |
6.5 |
| 42 |
177.0 |
162.2 |
11.9 |
168.1 |
178.0 |
10.4 |
159.0 |
196.1 |
9.0 |
149.7 |
216.7 |
7.7 |
133.5 |
226.2 |
6.6 |
| 44 |
183.0 |
165.2 |
12.1 |
173.8 |
181.0 |
10.6 |
164.5 |
199.3 |
9.2 |
154.9 |
220.0 |
7.9 |
136.2 |
225.5 |
6.8 |
| 45 |
186.1 |
166.7 |
12.2 |
176.7 |
182.6 |
10.7 |
167.2 |
200.9 |
9.3 |
157.5 |
221.6 |
8.0 |
137.0 |
223.8 |
6.9 |
| 46 |
189.1 |
168.2 |
12.3 |
179.7 |
184.1 |
10.8 |
170.0 |
202.5 |
9.3 |
160.1 |
223.3 |
8.0 |
137.9 |
222.1 |
7.0 |
| 48 |
195.3 |
171.3 |
12.5 |
185.6 |
187.4 |
11.0 |
175.6 |
205.8 |
9.5 |
165.4 |
226.7 |
8.2 |
138.6 |
216.8 |
7.2 |
| 50 |
201.7 |
174.4 |
12.7 |
191.6 |
190.6 |
11.1 |
181.4 |
209.2 |
9.7 |
170.9 |
230.2 |
8.3 |
140.2 |
213.4 |
7.4 |
| 55 |
217.9 |
182.6 |
13.1 |
207.1 |
199.1 |
11.6 |
196.1 |
218.0 |
10.1 |
184.8 |
239.4 |
8.7 |
143.1 |
202.2 |
7.9 |
Notes :
1. Ratings based on sea level altitude and evaporator fouling
factor of 0.00025
2. Consult Trane representative for performance at
temperature outside of the ranges shown.
3. kW input is for compressors only.
4. EER = Energy Efficient Ratio (Btu/watt-hour). Power inputs
include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 10
F.
6. 115 F Performance data reflect Adaptive Control
Microprocessor control algorithms.
7. Interpolation is permitted, extrapolation is not.
8. Rated in accordance with ARI Standard 590-92.
Metric |
Entering
Condenser Air temperature (Degrees C) |
| LWT (Deg C) |
30 |
35 |
40 |
45 |
| kWo |
kWi |
COP |
kWo |
kWi |
COP |
kWo |
kWi |
COP |
kWo |
kWi |
COP |
| 6 |
595.8 |
181.0 |
3.0 |
566.8 |
197.4 |
2.7 |
537.0 |
216.0 |
2.3 |
485.3 |
224.3 |
2.0 |
| 8 |
632.5 |
186.6 |
3.1 |
601.7 |
203.2 |
2.7 |
570.1 |
221.9 |
2.4 |
501.6 |
221.6 |
2.1 |
| 10 |
670.1 |
192.4 |
3.2 |
637.8 |
209.2 |
2.8 |
604.6 |
228.1 |
2.5 |
514.5 |
216.8 |
2.2 |
Notes :
1. Evaporator fouling factor is 0.00025 per ARI Standard
550-92
2. Interpolation between points is permissible. Extrapolation
is not permitted.
3. kWi input is for the compressors only.
4. COP = Coefficient of Performance (kWo/kWi).Power includes
compressors, condenser fans and control power.
5. Rated in accordance with ARI Standard 590-92.
6. Ratings are based on an evaporator temperature drop of 5.6
C.
. |