| Electrical Data Table E-1 - Electrical Data (60 Hz, 3 Phase)(Continued)
| Unit
Size |
Unit
Wiring |
Motor
Data |
| |
|
|
|
Compressor
(Ea) |
|
|
|
|
|
| Rated Voltage |
MCA(4)
Ckt1/Ckt2(1)(2) |
MOP(3) |
Rec Time Delay or
RDE(5) |
Qty. |
RLA(6) |
LRA(9) |
Qty. |
KW |
Fans (Ea) FLA |
Control KW(8) |
| RTAA 215 |
200 |
537/537 |
800/800 |
700/700 |
2 |
393/393 |
2391/2391 |
14 |
1.3 |
6.5 |
0.75 |
| |
230 |
537/537 |
800/800 |
700/700 |
2 |
393/393 |
2391/2391 |
14 |
1.3 |
6.5 |
0.75 |
| |
380 |
517 |
700 |
600 |
2 |
208/208 |
1085/1085 |
14 |
1.3 |
3.5 |
0.75 |
| |
460 |
424 |
500 |
500 |
2 |
171/171 |
896/896 |
14 |
1.3 |
2.8 |
0.75 |
| |
575 |
340 |
450 |
400 |
2 |
137/137 |
725/725 |
14 |
1.3 |
2.3 |
0.75 |
| RTAA 240 |
380 |
366/275 |
500/450 |
450/350 |
3 |
147-147/200 |
766-766/1085 |
17 |
1.3 |
3.5 |
1.0 |
| |
460 |
303/224 |
400/350 |
350/300 |
3 |
122-122/163 |
633-633/896 |
17 |
1.3 |
2.8 |
1.0 |
| |
575 |
244/180 |
300/300 |
300/225 |
3 |
98-98/131 |
512-512/725 |
17 |
1.3 |
2.3 |
1.0 |
| RTAA 270 |
380 |
439/275 |
600/450 |
500/350 |
3 |
200-147/200 |
1085-766/1085 |
19 |
1.3 |
3.5 |
1.0 |
| |
460 |
360/224 |
500/350 |
450/300 |
3 |
163-122/163 |
896-633/896 |
19 |
1.3 |
2.8 |
1.0 |
| |
575 |
290/180 |
400/300 |
350/225 |
3 |
131-98/131 |
725-512/725 |
19 |
1.3 |
2.3 |
1.0 |
| RTAA 300 |
380 |
499/275 |
600/450 |
600/350 |
3 |
200-200/200 |
1085-1085/1085 |
21 |
1.3 |
3.5 |
1.0 |
| |
460 |
406/224 |
500/350 |
450/300 |
3 |
163-163/163 |
896-896/896 |
21 |
1.3 |
2.8 |
1.0 |
| |
575 |
327/180 |
450/300 |
400/225 |
3 |
131-131/131 |
725-725/725 |
21 |
1.3 |
2.3 |
1.0 |
| RTAA 340 |
380 |
366/499 |
500/600 |
450/600 |
3 |
147-147/200-200 |
766-766/1085-1085 |
24 |
1.3 |
3.5 |
1.0 |
| |
460 |
303/406 |
400/500 |
350/450 |
4 |
122-122/163-163 |
633-633/896-896 |
24 |
1.3 |
2.8 |
1.0 |
| |
575 |
244/327 |
300/450 |
300/400 |
4 |
98-98/131-131 |
512-512/725-725 |
24 |
1.3 |
2.3 |
1.0 |
| RTAA 370 |
380 |
439/499 |
600/600 |
500/600 |
3 |
200-147/200-200 |
1085-766/1085-1085 |
26 |
1.3 |
3.5 |
1.0 |
| |
460 |
360/406 |
500/500 |
450/450 |
4 |
163-122/163-163 |
896-633/896-896 |
26 |
1.3 |
2.8 |
1.0 |
| |
575 |
290/327 |
400/450 |
350/400 |
4 |
131-98/131-131 |
725-512/725-725 |
26 |
1.3 |
2.3 |
1.0 |
| RTAA 400 |
380 |
499/499 |
600/600 |
600/600 |
3 |
200-200/200-200 |
1085-1085/1085-1085 |
28 |
1.3 |
3.5 |
1.0 |
| |
460 |
406/406 |
500/500 |
450/450 |
4 |
163-163/163-163 |
896-896/896-896 |
28 |
1.3 |
2.8 |
1.0 |
| |
575 |
327/327 |
450/450 |
400/400 |
4 |
131-131/131-131 |
725-725/725-725 |
28 |
1.3 |
2.3 |
1.0 |
|
Notes :
1. All 70 - 125 ton units are single point power.
2. 130 - 215 ton low voltage units and 240-400 ton units
require separate power connections for each circuit.
3. MOP - Maximum Overcurrent Protection - may be either
fused/HACR type breaker (UL/CSA) or with circuit breaker (CSA only).
MOP = 225 percent of the largest
compressor RLA plus 100 percent of the second compressor RLA, plus the sum of the
condenser fans FLA per NEC 440-22. (Use FLA per circuit, NOT FLA for entire unit)
4. MCA- Minimum Circuit Ampacity- 125 percent of largest
compressor RLA plus 100 percent of second compressor plus the sum of the condenser fans
FLA per NEC 440-33.
5. RECOMMENDED TIME DELAY OR DUAL ELEMENT (RDE) FUSE SIZE:
150 percent of the largest compressor RLA plus 100 percent of the second compressor RLA
and the sum of the condenser fan FLAs.
6. RLA - Rated Load Amps - rated in accordance with UL
Standard 465.
7. Local codes may take precedence.
8. Control kw includes operational controls only. Does not
include evaporator heat tape.
9. LRA - Locked Rotor Amps - based on full winding (x-line)
start units. LRA for Y-Delta starters is 1/3 of LRA of X-Line units.
10. VOLTAGE UTILIZATION RANGE:
| Rated Voltage |
Utilization Range |
| 200 |
180-220 |
| 230 |
208-254 |
| 460 |
414-506 |
| 575 |
516-633 |
11. A 115/60/1, 15 amp, customer provided power connection
is required to operate the unit controls. A separate 115/60/1, 15 amp, customer provided
power connection is also needed to power the evaporator heat tape (420 watts @ 120 volts).
If the optional control power transformer is used, the customer needs only to provide a
power connection for the evaporator heat tape.
12. Low ambient unit will have one additional fan on most
sizes. MCA will not change. See pages 53-55 for number of fans on
low ambient units.