   Trane Company (The)  Series R Helical Rotary Liquid Chiller  

Series R Helical Rotary Liquid Chiller - Page 603

 

 

Features and Benefits

Options

Insulation

All low temperature surfaces are covered with 3/4 inch Armaflex II or equal (K = 0.28), including the evaporator and water boxes, suction line, motor housing and liquid/vapor separator.

Smooth Bore Condenser Tubes

Smooth bore copper tubes are available for high fouling water applications. Smooth bore condenser tubes are 3/4" diameter and .035 wall thickness.

Cupro-nickel Condenser Tubes

Cupro-nickel condenser tubes are available for special applications. 90/10 cupro-nickel tubes are 3/4" diameter and .035 wall thickness.

Refrigerant Isolation Valves

Factory installed condenser inlet and outlet refrigerant valves allow isolation of the full refrigerant charge in the condenser while servicing the chiller.

300 psig Evaporator Waterboxes

Waterboxes are designed for 300 psig maximum waterside working pressure. Grooved pipe water connections are provided for ease of installation.

Standard Ice Making

Controls and safeties to allow operation with brine temperatures greater than or equal to 20 F. Includes dual setpoints for ice making capability and daytime comfort cooling. A typical application would include Climatice ® ice storage system with daytime chiller operation above 40 F. (requires options module)

Options Module

Accepts generic building automation system inputs for current limit setpoint and chiller water setpoint via 2-10 VDC or 4-20 mA signal. Outputs a 2-10 VDC or 4-20 mA signal to a generic BAS to monitor compressor % RLA. Outputs a binary signal to a generic BAS for use with condenser limit control. Allows remote enable/disable of ice making operation.

Solid State Starter

An optional Solid State Starter is unit mounted with a NEMA 1 gasketed enclosure. To increase starter life, bypass contactors are provided to bypass current from the silicon control rectifiers (SCRs) after startup.

Non-fused Disconnect

The non-fused molded case disconnect switch (UL approved) is used to disconnect the chiller from main power and comes pre-wired from the factory with terminal block power connections. The external operator handle is lockable.

Circuit Breaker

A standard interrupting molded case capacity circuit breaker (UL approved) is available. The circuit breaker can also be used to disconnect the chiller from main power and comes pre-wired from the factory with terminal block power connections. The external operator handle is lockable.

High Interrupting Capacity Circuit Breaker

A high interrupting molded case capacity circuit breaker (UL approved) is also available. The circuit breaker can also be used to disconnect the chiller from main power and comes pre-wired from the factory with terminal block power connections. The external operator handle is lockable.

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2009 AECinfo.com