Electrical Data and Connections |
Compressor Motor Electrical Data (60 Hertz)
|
NominalVoltage |
200 |
230 |
380 |
460 |
575 |
| Compressor
Code |
Voltage
Utilization Range |
180 /
220 |
208 /
254 |
342 /
418 |
414 /
506 |
516 /
633 |
|
Max kW |
249 |
249 |
249 |
249 |
249 |
| C1,C2 |
RLA@MaxkW |
812 |
698 |
421 |
349 |
279 |
|
LRAY |
1173 |
936 |
558 |
469 |
375 |
|
LRAD |
3634 |
2901 |
1727 |
1453 |
1162 |
|
Max kW |
329 |
329 |
329 |
329 |
329 |
| D1, D2 |
RLC@Max kW |
1047 |
918 |
549 |
455 |
367 |
|
LRAY |
1690 |
1532 |
850 |
730 |
612 |
|
LRAD |
5477 |
4966 |
2755 |
2366 |
1984 |
Notes:
1. See Selection Procedure Section for details .
2. The RLA @ Max kW is based on the performance of the motor
developing full rated horsepower.
3. Electrical component sizing should be based off of actual jobsite
operating conditions. This can be obtained through the use of the Series R chiller
selection program available through local Trane sales offices.
Compressor Motor Electrical Data (50
Hertz)
|
NominalVoltage |
380 |
400 |
415 |
| Compressor
Code |
Voltage
Utilization Range |
342 /
418 |
360 /
440 |
374 /
457 |
| |
LRAY |
456 |
480 |
498 |
| |
LRAD |
1406 |
1488 |
1536 |
| |
Max kW |
274 |
275 |
274 |
| D1,D2,D3 |
RLA @ Max kW |
445 |
445 |
445 |
| |
LRAY |
711 |
748 |
776 |
| |
LRAD |
2303 |
2424 |
2515 |
Notes:
1. See Selection Procedure Section for details .
2. The RLA @ Max kW is based on the performance of the motor
developing full rated horsepower.
3. Electrical component sizing should be based off of actual jobsite
operating conditions. This can be obtained through the use of the Series R chiller
selection program available through local Trane sales offices.
Electrical Connections
| Starter Panel
Connection |
Selection RLA |
LugSize
L1-L3(EachPhase) |
| Terminals
Only |
000-760 |
(2 )#4-500 MCM |
| 761-935 |
(4) 4/0-500 MCM |
| Main Circuit Breaker or Non-Fused
Disconnect Switch |
000-185 |
(1) #4-350 MCM |
| 186-296 |
(2) 2/0-250 MCM |
| 297-444 |
(2) 3/0-350 MCM |
| 445-592 |
(2) #1-500 MCM |
| 593-888 |
(4) 4/0-500 MCM |
Note:
1. Lug sizes are independent of starter type.