rlc609a.jpg (2606 bytes) Electrical Data and Connections

Compressor Motor Electrical Data (60 Hertz)

NominalVoltage 200 230 380 460 575
Compressor Code Voltage Utilization Range 180 / 220 208 / 254 342 / 418 414 / 506 516 / 633
Max kW 249 249 249 249 249
C1,C2 RLA@MaxkW 812 698 421 349 279
LRAY 1173 936 558 469 375
LRAD 3634 2901 1727 1453 1162
Max kW 329 329 329 329 329
D1, D2 RLC@Max kW 1047 918 549 455 367
LRAY 1690 1532 850 730 612
LRAD 5477 4966 2755 2366 1984

Notes:

1. See Selection Procedure Section for details .

2. The RLA @ Max kW is based on the performance of the motor developing full rated horsepower.

3. Electrical component sizing should be based off of actual jobsite operating conditions. This can be obtained through the use of the Series R chiller selection program available through local Trane sales offices.

Compressor Motor Electrical Data (50 Hertz)

NominalVoltage 380 400 415
Compressor Code Voltage Utilization Range 342 / 418 360 / 440 374 / 457
  LRAY 456 480 498
  LRAD 1406 1488 1536
  Max kW 274 275 274
D1,D2,D3 RLA @ Max kW 445 445 445
  LRAY 711 748 776
  LRAD 2303 2424 2515

Notes:

1. See Selection Procedure Section for details .

2. The RLA @ Max kW is based on the performance of the motor developing full rated horsepower.

3. Electrical component sizing should be based off of actual jobsite operating conditions. This can be obtained through the use of the Series R chiller selection program available through local Trane sales offices.

Electrical Connections

Starter Panel Connection Selection RLA LugSize L1-L3(EachPhase)
Terminals Only 000-760 (2 )#4-500 MCM
761-935 (4) 4/0-500 MCM
Main Circuit Breaker or

Non-Fused

Disconnect Switch

000-185 (1) #4-350 MCM
186-296 (2) 2/0-250 MCM
297-444 (2) 3/0-350 MCM
445-592 (2) #1-500 MCM
593-888 (4) 4/0-500 MCM

Note:

1. Lug sizes are independent of starter type.

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2009 AECinfo.com