| Mechanical Specifications Clear Language Display Panel
Factory mounted to the door of the control panel, the operator interface shall have a 16 button keypad for operator
input and a two line by 40 character display screen. A
chiller report, refrigerant report, compressor report, an operator configurable custom report, operator settings, service settings,
service tests, and diagnostics may thus be accessed.
All diagnostics and messages shall be displayed in "clear language."
The data contained in the Chiller Report, Refrigerant Report, and Compressor Report shall include:
- All water temperatures and setpoints
- Current chiller operating mode
- Diagnostic history
- Control source (i.e. local panel, external source, remote BAS)
- Current limit setpoint
- Outdoor air temperature (optional)
- Saturated refrigerant temperatures and pressures
- Compressor starts and hours running
- Line currents
- Line voltages (optional)
- Refrigerant detection external to chiller in ppm (refrigerant monitor not supplied
by chiller manufacturer)
- Approach temperatures Mechanical
Specification
All necessary settings and setpoints shall be programmed into the microprocessor
controller via the keypad of the operator interface.
The controller shall be capable of receiving signals from a variety of control sources (which shall not be mutually exclusive
i.e. any combination of control sources can coexist
simultaneously) and shall be capable of being programmed at the keypad as to which control source has priority. Control sources
can be:
- the local operator interface (standard)
- a 4-20 mA or 2-10 VDC signal from an external source (interface optional) (control source not supplied by chiller manufacturer)
- Tracer ® or Tracer Summit (interface optional) (Tracer and Tracer Summit supplied by Trane)
- Generic BAS (interface optional) (control source not supplied by chiller manufacturer)
The control source with priority shall then determine the active setpoints via the signal that is sent to the control panel.
Unit Mounted Starter
A NEMA 1 type enclosure with top power wiring access and three-phase solid-state
overload protection. Starters shall be available in a
Wye-Delta configuration. The starter shall be factory mounted and completely prewired
to the compressor motor and the control panel. A
factory installed and wired 600VA control power transformer provides all unit control power (120 VAC secondary) as well as UCP2
module power (24 VAC secondary). Optional starter
features include: Circuit breakers and mechanical non-fused disconnects. Worldwide
Applied Systems Group The Trane Company 3600 Pammel Creek Road La Crosse,
WI 54601-7599 www.trane.com An American Standard Company
| Library |
Product
Literature |
| Product Section |
Refrigeration |
| Product |
Rotary
Liquid Chiller |
| Model |
000 |
| LiteratureType |
Data Sales
Catalog |
| Sequence |
6 |
| Date |
July 1998 |
| FileNo. |
PL-RF-RLC-000-DS-6-798 |
| Supersedes |
September 1997 |
| OrderingNo. |
RLC-DS-6 |
Since The Trane Company has a policy of
continuous product improvement, it reserves the right to change design and specification
without notice.
Worldwide Applied Systems Group
The Trane Company
3600 Pammel Creek Road
La Crosse, WI 54601-7599
www.trane.com
An American Standard Company |