Packaged Rooftop Air Conditioners - RT-DS-8 - Page 808

 

 

rtds807a.jpg (2606 bytes) General Data

 

Table 9-1 — General Data — 50-75 Ton
50 Ton 55Ton 60Ton 70 Ton 75 Ton
CompressorData3 Standard Standard
Number/Size (Nominal) 2/10,2/15 Ton 4/15 Ton 4/15 Ton 4/10, 2/15 Ton 4/10,2/15 Ton 2/10,2/15 Ton
Model Scroll Scroll Scroll Scroll Scroll
Unit CapacitySteps(%) 100/80/60/30 100/75/50/25 100/75/50/25 100/72/44/22 100/72/44/22 100/69/38/19
RPM 3450 3450 3450 3450 3450
Evaporator Fans
Number/Size/Type 2/20"/FC 2/20"/FC 2/22"/FC 2/22"/FC 2/22"/FC
Number of Motors 1 1 1 1 1
  Hp Range 7-1/2-30 7-1/2-30 10-40 10-40 10-40
  Cfm Range1 10000-22500 12000-24000 14000-27000 16000-27000 16000-27000
ESP Range—(In WG) 0.25-4.0 0.25-4.0 0.25-4.0 0.25-4.0 0.25-4.0
Exhaust Fans 50% 100% 50% 100% 50% 100% 50% 100% 50% 100%
Number/Size/Type 1/18"/FC 2/18"/FC 1/18"/FC 2/18"/FC 1/20"/FC 2/20"/FC 1/20"/FC 2/20"/FC 1/20"/FC 2/20"/FC
 Hp Range 5-7.5 5-15 5-7.5 5-15 5-7.5 5-20 5-7.5 5-20 5-7.5 5-20
Cfm Range 3000-11000 9000-20000 3000-11000 10000-215000 4000-13000 12000-27000 4000-13000 12000-27000 Cfm Range
ESPRange—(In.WG) 0.25-1.4 0.2-2.0 0.25-1.4 0.2-2.0 0.25-1.4 0.2-2.0 0.25-1.4 0.2-2.0 0.25-1.4 0.2-2.0
Condenser Fans
Number/Size/Type 6/26"/Prop 6/26"/Prop 6/26"/Prop 6/26"/Prop 6/26"/Prop
Hp(Each) 1.0 1.0 1.0 1.0 1.0
Cfm 36600 36600 40800 40800 40800
Cycle/Phase 1/2/Enhanced 1/2/Enhanced 1/2/Enhanced 1/2/Enhanced 1/2/Enhanced
Evaporator Coil— Standard
Size(Ft2) 37.9 37.9 43.1 43.1. 43.1
Rows/Fin Series 2/144 2/144 2/156 2/168 4/144
TubeDiameter/Surface 1/2/Enhanced 1/2/Enhanced 1/2/Enhanced 1/2/Enhanced 1/2/Enhanced
Evaporator Coil High Capacity
Size(Ft2) 37.9 37.9 43.1 NA 43.1
  Rows/Fin Series 4/144 4/144 4/144 4/144
TubeDiameter/Surface 1/2/Enhanced 1/2/Enhanced 1/2/Enhanced 1/2/Enhanced
Condenser Coil(Aluminum Fins)
Size(Ft2) 70.0 70.0 88.0 88.0 88.0
Rows/Fin Series/TubeDiameter 3/144/-3/8 3/144/-3/8 3/144/-3/8 3/144/-3/8 3/144/-3/8
Copper Condenser Fins(Optional) 3/144/-3/8 3/144/-3/8 3/144/-3/8 3/144/-3/8 3/144/-3/8
Electric Heat
KW Range 70-190 70-190 90-190 90-190 90-190
Capacity Steps: 3 3 3 3 3
Natural Gas Heat
Standard Gas Heat
Low Heat Input 500 500 500 500 500
Low Heat Input 850 850 850 850 850
Standard Heating Capacity Steps: 2 2 2 2 2
Modulating Gas Heat
High/low Heat- Limited Modulation 33% 33% 33% 33% 33%
Heat Exchanger Type Standard Standard Standard Standard Standard
High/low Heat- Limited Modulation 100% 100% 100% 100% 100%
Heat Exchanger Type High Grade, Stainless Steel High Grade, Stainless Steel High Grade, Stainless Steel High Grade, Stainless Steel High Grade, Stainless Steel
Hot Water Coil
Size(Inches) 44x66x2 Row 44x66x2 Row 42x90x2 Row 42x90x2 Row 42x90x2 Row
Type Type W, Prima Flo Type W, Prima Flo Type W, Prima Flo Type W, Prima Flo Type W, Prima Flo
High Heat(Fins/Ft) 110 110 110 110 110
Low Heat(Fins/Ft) 80 80 80 80 80
SteamSteam Coil
Size(Inches) 30x66x1 Row 30x66x1 Row 30x99x1 Row 30x99x1 Row 30x99x1 Row
12X66X1 12X66X1 12X90X1 12X90X1 12X90X1
Type Type NS Type NS Type NS Type NS Type NS
High Heat(Fins/Ft) 96 96 72 72 72
Low Heat(Fins/Ft) 42 42 42 42 42
Filters
 Panel Filters
Number/Size(Inches) 20-20X25X2 20-20X25X2 35-16X20X2 35-16X20X2 35-16X20X2
Face Area(Ft²) 69.4 69.4 77.8 77.8 77.8
Bag Filters
Number/Size(Inches) 3-12X24X19 3-12X24X19 6-12X24X19 6-12X24X19 6-12X24X19
9-12X24X19 9-12X24X19 8-12X24X19 8-12X24X19 8-12X24X19
3-12X24X19 3-12X24X19 6-12X24X19 6-12X24X19 6-12X24X19
9-12X24X19 9-12X24X19 8-12X24X19 8-12X24X19 8-12X24X19
3-12X24X19 3-12X24X19 6-12X24X19 6-12X24X19 6-12X24X19
9-12X24X19 9-12X24X19 8-12X24X19 8-12X24X19 8-12X24X19
Face Area(Ft²) 42.0 42.0 44.0 44.0 44.0
Standard Unit Minimum OutsideAir Temperature Dor Mechinical Cooling
Without Hot Gas Option 35F 40F 30F 45F 45F
With Hot Gas Option 35F 40F 30F 45F 45F
Low Ambient Option Minimum Outside Air Temperature
Without Hot Gas Option 0 F 0 F 0 F 0 F 0 F
With Hot Gas Option 10 F 10 F 10 F 10 F 10 F

Notes:

1. For cfm values outside these ranges, refer to RT-EB-104.

2. Refer to Table 35-3 for availability of electric heat kw ranges by voltage.

3. 20-30 Ton models are single circuit, 40 Ton models are dual circuit.

4. The firing rate of the unit can vary from 33% of the Heater Mbh up to the nameplate rating of the unit.

5. The firing rate of the unit can vary from pilot rate of 125,000 Btuh up to the nameplate rating of the unit

 

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    