Homepage  
Search
find:
search for:
   
 
Site Navigation
News / Publications
Jobs
Service
   Add this page to Google Bookmarks
   Add this page to Mister Wong
   Add this page to del.icio.us
 
   Trane Company (The)  Packaged Rooftop Air Conditioners -RT-DS-8  

Packaged Rooftop Air Conditioners - RT-DS-8 - Page 810

 

 

rtds810a.jpg (2606 bytes) General Data

Table 11-1 — ARI Performance Data1

Tons Model (MBh) EER IPLV2
         
  SAHFC2040A**A**A***** 220 9.5 12.8
  SXHFC2040A**A**A***** 220 9.5 12.8
20 SFHFC204LA**A**A***** 220 9.4 12.7
  SEHFC204*A**A**A***** 220 9.4 12.7
  SLHFC204LA**A**A***** 220 9.4 12.6
    220 9.4 12.7

Notes:

1. This information is rated in accordance to the ARI Standard 360-86 for large unitary equipment up to 20 tons. These Trane products can be found in the current ARI  Directory.

2. IPLV — Integrated Part Load Value

3. This information applies to units whose design sequence (Digit 10) is "A" or later.

Table 11-2 — ARI Correction Multipliers

  Model Digit Designator   Multipliers (%)
OptionDescriptio n     Capacity EER IPLV
High Heat Gas 9 H,J,P 100 100 100
High Heat Steam 9 H 100 99 98
High Heat Hot Water 9 H 100 99 99
Wire Mesh Filter 13 B 100 101 101
95% Bag filter 13 D 99 95 91
95% Cartridge Filter 13 E 99 95 92
100% Economizer 16 D 100 99 98
High Capacity Coil 21 G 114 109 107
High Efficiency Motor 21 L 100 101 101
Inlet Guide Vanes 17 3 100 99 99
VFD(60 Hz) 17 6-9 99 98 98

 

Table 11-3 — Economizer Outdoor Air Damper Leakage (Of Rated Airflow)

  delta P Across Dampers (In. WC)
  0.5 (In.) 1.0 (In.)
Standard L"ow Leak" 1.5% 2.5%
Optional"Ultra Low Leak" 0.5% 1.0%

Note: Above data based on tests completed in accordance with AMCA Standard 575 at AMCA Laboratories.

Application Considerations

EXHAUST AIR OPTIONS

When is it necessary to provide building exhaust? Whenever an outdoor air economizer is used, a building generally requires an exhaust system. The purpose of the exhaust system is to exhaust the proper amount of air to prevent over or underpressurization of the building. The goal is to exhaust approximately 10 percent less air than the amount of outside air going into the building. This maintains a slightly positive building pressure.

A building may have all or part of its exhaust system in the rooftop unit. Often, a building provides exhaust external to the air conditioning equipment. This external exhaust must be considered when selecting the rooftop exhaust system.

IntelliPak® Rooftop units offer four types of exhaust systems:

1.

100 percent modulating exhaust with Statitrac™ direct space sensing building pressurization control (with or without variable frequency drives).

2.

100 percent modulating exhaust without Statitrac.

3.

50 percent power exhaust.

4.

Barometric relief dampers.

Application Recommendations

1.

100 percent modulating exhaust with Statitrac™ control


For both CV and VAV rooftops, the 100 percent modulating exhaust discharge dampers (or VFD) are modulated in response to building pressure. A differential pressure control system, called Statitrac™, uses a differential pressure transducer to compare indoor building pressure to atmospheric pressure. The FC exhaust fan is turned on when required to lower building static pressure to setpoint. The Statitrac control system then modulates the discharge dampers (or VFD) to control the building pressure to within the adjustable, specified dead band that is set at the Human Interface Panel.

Advantages of the Statitrac™ 100 percent modulating exhaust system are:

a

The exhaust fan runs only when needed to lower building static pressure.

b

Statitrac compensates for pressure variations within the building from remote exhaust fans and makeup air units.

c

The exhaust fan discharges in a single direction resulting in more efficient fan operation compared to return fan systems.

d

Because discharge dampers modulate the airflow, the exhaust fan may be running unloaded whenever the economizer dampers are less than 100 percent open.

With an exhaust fan system, the supply fan must be sized to pull the return air back to the unit through the return system during non-economizer operation. However, a supply fan can typically overcome return duct losses more efficiently than a return air fan system. Essentially, one large fan by itself is normally more efficient than two fans in series because of only one drive loss not two as with return air systems.

The reason for either a return air fan or an exhaust fan is to control building pressure. The Trane 100 percent modulating exhaust system with Statitrac does a better job controlling building pressure than return fans simply because 100 percent modulating exhaust discharge dampers (or VFD) are controlled directly from building pressure, rather than from an indirect indicator of building pressure such as outdoor air damper position.

The 100 percent modulating exhaust system with Statitrac may be used on any rooftop application that has an outdoor air economizer. However, when most exhaust is handled external to the rooftop or when building pressure is not critical, one of the other less expensive methods of exhaust may be used.

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2009 AECinfo.com