| Application Considerations
of avoiding an acoustical problem is to place any rooftop equipment away from
acoustically critical area. If possible, rooftop
equipment should not be located directly above areas
such as: offices, conference rooms, executive office areas and classrooms. Ideal
locations are above corridors, utility rooms, toilet
facilities, or other areas where higher sound levels are acceptable.
Several basic guidelines for unit placement should be followed to minimize sound
transmission through the building structure:
1
Never cantilever the condensing section of the unit. A structural cross member
must support this end of the unit.
2
Locate the units center of gravity close to or over a column or main support
beam to minimize roof deflection and vibratory noise.
3
If the roof structure is very light, roof joists should be replaced by a structural
shape in the critical areas described above.
4
If several units are to be placed on one span, they should be staggered to reduce deflection over that span. It is
impossible to totally quantify the effect of building
structure on sound transmission, since this depends on
the response of the roof and building members to the sound and vibration of the unit components. However, the guidelines
listed above are experience proven guidelines which
will help reduce sound transmission.
There are several other sources of unit sound, i.e., supply fan, compressors,
exhaust fans, condenser fans and aerodynamic noise generated at the duct fittings. Refer to the ASHRAE Applications Handbook,
Chapter 42, 1991 edition for guidelines for minimizing
the generation of aerodynamic noise associated with duct fittings.
Tranes Engineering BulletinRT-EB-80 describes various
duct installation considerations specifically addressing indoor sound level concerns.
This bulletin includes sound power data on Tranes
IntelliPak Rooftops 20 through 130 tons. Ask your local Trane representative for this informative engineering bulletin.
The VariTraneŽ Computerized Duct Design Program can be used to analyze the
truck duct, run-out duct, VAV control unit and terminal
unit noise attenuation. This program quantifies the airborne sound generation
that can be expected in each terminal so that the
designer can identify potential sound problems and
make design alterations before equipment installation.
The Trane Acoustics Program (TAP) allows modeling of rooftop installation parameters.
The output of this program shows the resulting indoor
NC level for the modeled installation. This program is available from Tranes Customer Direct Service Network (C.D.S.), ask your local Trane representative
for additional information on this program.
Clearance Requirements
The recommended clearances identified with unit dimensions should be
maintained to assure adequate serviceability, maximum
capacity and peak operating efficiency. A reduction
in unit clearance could result in condenser coil starvation or warm condenser
air recirculation. If the clearances shown are not
possible on a particular job, consider the following:
- Do the clearances available allow for major service work such as changing compressors or coils?
- Do the clearances available allow for proper outside air intake, exhaust air removal and condenser airflow?
- If screening around the unit is being used, is there a possibility of air recirculation from the exhaust to the outside
air intake or from condenser exhaust to condenser
intake?
Actual clearances which appear inadequate should be reviewed with a local
Trane sales engineer. When two or more units are to be
placed side by side, the distance between the units should be increased to 150
percent of the recommended single unit clearance.
The units should also be staggered as shown in Figure 17-1 for two reasons:
1
To reduce span deflection if more than one unit is placed on a single span. Reducing deflection discourages sound
transmission.
2
To assure proper diffusion of exhaust air before contact with the outside air intake of adjacent unit. Application Considerations |