Trane Company (The)
Packaged Rooftop Air Conditioners -RT-DS-8
Packaged Rooftop Air Conditioners - RT-DS-8 - Page 816
Packaged Rooftop Air Conditioners -RT-DS-8
Figure 17-1 Unit Placement Figure
*50 Through 130 Ton Rooftop Units have two outdoor air intakes. 17-2 Duct Design
Duct Design It is important to note that the rated capacities of the rooftop can be met only if the rooftop is properly installed in the field. A well-designed duct system is essential in meeting these capacities. The satisfactory distribution of air throughout the system requires that there be an unrestricted and uniform airflow from the rooftop discharge duct. This discharge section should be straight for at least several duct diameters to allow the conversion of fan energy from velocity pressure to static pressure. However, when job conditions dictate elbows be installed near the rooftop outlet, the loss of capacity and static pressure may be reduced through the use of guide vanes and proper direction of the bend in the elbow. The high velocity side of the rooftop outlet should be directed at the outside radius of the elbow rather than the inside as illustrated in Figure 17-2. |








